2003-08-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 3401.7.2.4HURRICANE MISSILE
 IMPACT PROTECTION SHUTTERS WILL BE
 REQUIRED ON THE NEW WINDOWS IF THE AREA
 OF GLASS IN THE NEW WINDOWS EXCEEDS 25%
 OF THE TOTAL GLAZED AREA OF THE WHOLE
 RESIDENCE.PROVIDE A PRODUCT APPROVAL
 FOR SHUTTERS FOR THE NEW WINDOWS OR
 SUBMIT DETAILS TO VERIFY THAT THE NEW
 WINDOW GLASS AREA IS LESS THAN 25% OF
 THE GLAZED AREA OF THE WHOLE RESIDENCE.
  
 4) FBC 1707.4.2MIAMI-DADE PRODUCT
 APPROVAL, ICC-ES EVALUATION REPORT OR
 SITE-SPECIFIC ENGINEER'S CERTIFICATION
 IS REQUIRED FOR THE PROPOSED WINDOWS.
 THE NOTICE OF EVALUATION SUBMITTED FOR
 THE AMERICAN CRAFTSMAN SINGLE HUNG
 WINDOW IS NOT SUFFICIENT.BLANK COPIES
 OF THE PRODUCT APPROVAL SUBMITTAL FORM
 ARE ATTACHED, FOR USE IF THE SITE-
 SPECIFIC ENGINEERING OPTION IS TO BE
 PURSUED.
  
 5) FBC* 104.2.1THE DRAWING TITLE BLOCK
 IS NOT PRINTED CLEARLY.ALL DRAWINGS
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 6) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ALSO, THE PLANS
 SHALL CITE FLORIDA BUILDING CODE 2001
 (WITH REVISIONS AS OF JUNE 2003) AS THE
 BASIS OF THE DESIGN.
  
 7) FBC 1606.2.2 WALL SECTION - ANCHORING
 OF 2X6 BASE PLATE.ANNOTATE THE PLANS
 TO STATE WHAT THE PROPOSED RED HEAD
 ANCHORS WILL BE BOLTED INTO AT 24" O.C.
  
 8) FBC 1606.2.2WALL SECTION.THE
 STRAPS SPECIFIED ARE SIMPSON HETAL 16
 (ANNOTATION IS NOT PRINTED CLEARLY ON
 THE PLANS).THIS TYPE OF ANCHOR IS
 DESIGNED FOR EMBEDMENT IN THE TIE BEAM
 AND IS NOT SUITABLE FOR THE PROPOSED
 USE.SPECIFY AN ALTERNATIVE ANCHOR
 CAPABLE OF RESISTING THE LALETRAL LOADS
 DUE TO WIND PRESSURES IN THE WALL. ALSO,
 ADD DIMENSIONS TO THE WALL SECTION TO
 SHOW THE HEIGHT OF THE EXISTING CMU WALL
 AND THE OVERALL WALL HEIGHT.
  
 9) FBC 2308.3WOOD FRAMING AROUND DOOR
 AND WINDOW OPENINGS.AMEND THE PLANS TO
 SHOW THE WOOD FRAMING AROUND THE NEW
 WINDOWS AND THE DOOR.THE STRAPS AND
 ANCHORS SHALL RESIST THE LATERAL LOADS
 DUE TO WIND PRESSURES ON THE WINDOW/DOOR
 AND ADJACENT FRAMED WALL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN