2003-09-24 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 6) 61G15-23.002(2) ENGINEERS SHALL LEGI-
 BLY INDICATE THEIR NAME, ADDRESS, AND
 LICENSE NUMBER ON EACH SHEET. NO LICENSE
 NUMBER SHOWN.
 7) PIPING SCHEMATIC DOES NOT REFLECT THE
 POOL LAYOUT. LAYOUT DOES NOT HAVE A
 CLEANING LINE, 4 MAIN DRAINS, VENTS, SPA
 JETS, FOUNTAIN OR HEATER.
 8) DRAIN DETAIL DOES NOT REFLECT THE
 POOL LAYOUT. ONLY ONE DRAIN SHOWN ON THE
 POOL LAYOUT. ALSO SHOW WHERE THE VENT IS
 CONNECTED.
 9) INDICATE SIZE OF MAIN DRAIN.
 10) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
  