Date Text
2003-08-01 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY NEW OR EXISTING
 LIGHTING FOR NEW ROOMS AND EGRESS LIGHT-
 -ING ON STAIRS AND EXITS. EM LTS ETC.
 LS 101, CHAPT 5-8 SOME SHOWN, SEE FIRE
 REVIEW COMMENTS FOR ANY ADDITIONAL REQ'D
 2)NOTE: PLEASE SHOW ALL NEW ELECTRICAL
 CIRCUITING AND CORRELATE W/ A SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE 600.5 FOR NEW OR
 EXSITING SIGN CIRCUIT? BLDG USE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]