| 2003-08-13 00:00:00 | ******CORRECTIONS******* |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 3.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN. |
| | |
| | 4.)NOTE #1, BOTTOM OF THE FOUNDATION |
| | IS SHOWN AS 8" BELOW GRADE; FBC1804.1.3 |
| | REQUIRES THE BOTTOM OF FOUNDATIONS TO |
| | EXTEND NO LESS THAN 12" BELOW FINISH |
| | GRADE. |
| | |
| | 5.)ENERGY CALCS REQUIRED, FBC13-101.2. |
| | |
| | 6.)HAVE AN ENGINEER CERTIFY THE |
| | STRUCTURAL DESIGN. |
| | |
| | 7.)AT THE LAUNDRY ROOM, THERE IS A |
| | NOTE TO "REUSE EXISTING 2668 DOOR". TO |
| | REUSE THE DOOR, TWO COPIES OF A PRODUCT |
| | APPROVAL OR TEST REPORT FOR THAT DOOR |
| | MUST BE PROVIDED. |
| | |
| | 8.)VENTILATION REQUIRED FOR CRAWL |
| | SPACE TO COMPLY WITH FBC1804.6.3. |
| | |
| | 9.)PROVIDE UPLIFT FOR THE ATTACHMENTS. |
| | |
| | 10.) PROVIDE DESIGN INFORMATION |
| | REQUIRED TO BE ON THE PLAN FBC1606.1.7. |
| | |
| | 11.) IMPACT PROTECTION REQUIRED FOR |
| | GLAZING, FBC1606.1.4. |
| | |
| | 12.)THE PLAN SHOWS THAT THE ROOF IS |
| | TO BE REPLACED WITH TILE.PROVIDE AN |
| | ENGINEER'S LETTER CERTIFYING THAT THE |
| | TRUSSES CAN ACCOMODATE THE ADDITIONAL |
| | LOAD. |
| | |
| | 13.)FLOOR JOISTS TO COMPLY WITH FBC |
| | 2304.3.4 (PRESSURE TREATED). |
| | |
| | 14.)FIRESTOP REQUIRED, FBC705.3 (ALL |
| | WALLS AND PARTITION WALLS). |
| | |
| | 15.)THE NEW GALLERY BLOCKS THE ONLY |
| | EMERGENCY EGRESS FOR THE ADJACENT |
| | BEDROOM.SLEEPING ROOMS ARE REQUIRED |
| | TO COMPLY WITH FBC1005.4.PLEASE |
| | ADDRESS. |
| | |
| | 16.)PROVIDE TWO COPIES OF PRODUCT |
| | APPROVALS FOR: |
| | 2668 DOOR |
| | 2668 FRENCH DOOR |
| | SINGLE HUNG WINDOW |
| | ROOF TILE |
| | ROOF SHINGLES |
| | IMPACT PROTECTION |