| Plan Review Notes For Permit 03072019 |
| Permit Number |
03072019 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) CONTACT RODNEY COMPO, INDUSTRIAL PRE- | | | TREATMENT, ENVIRONMENTAL COMPLIANCE TO | | | SIZE GREASE INTERCEPTOR. (561) 837-4074 | | | 2) SEPARATE PERMIT REQUIRED FOR GREASE | | | INTERCEPTOR.WASTE ORD #2938-96 | | | 3) SEPARATE GAS PERMIT REQUIRED. | | | 4) SHT P-2 #7, CONDENSATE TO HAVE A | | | RELIEF VENT AS IT EXITS THE BLDG. | | | 5) SHT P-2 #13 NO TRAPS IN THE RELIEF | | | VALVE DISCHARGE LINE. 504.7.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|