2003-08-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) CONTACT RODNEY COMPO, INDUSTRIAL PRE-
 TREATMENT, ENVIRONMENTAL COMPLIANCE TO
 SIZE GREASE INTERCEPTOR. (561) 837-4074
 2) SEPARATE PERMIT REQUIRED FOR GREASE
 INTERCEPTOR.WASTE ORD #2938-96
 3) SEPARATE GAS PERMIT REQUIRED.
 4) SHT P-2 #7, CONDENSATE TO HAVE A
 RELIEF VENT AS IT EXITS THE BLDG.
 5) SHT P-2 #13 NO TRAPS IN THE RELIEF
 VALVE DISCHARGE LINE. 504.7.1
  
 REVIEW BY KEN STEVENS