| Plan Review Notes For Permit 03072014 |
| Permit Number |
03072014 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-01 00:00:00 | ********** UNSAT ******************** | | | | | | 1)NOTE: PLEASE PROVIDE ALL LICENSE | | | INFORMATION ON TITLE BLOCK AS REQ'D | | | UNDER FS-471, 61G15-23.004. | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS | | | SERVICE TO BE NEW? NO NOTES IF ALL | | | EXISTING? | | | | | | 3)NOTE: PLEASE SEE ALL SERVICE CONDUCTOR | | | -S.??350MCM FOR 600A'S, #1'S FOR 200A | | | MAIN DISC'S? PLEASE SIZE AND SHOW PER | | | 310.16 | | | 350MCM MENTIONS IN ONE 3' CONDCUIT? IS | | | THIS MEANT TO BE 2-3" CONDUITS? | | | | | | IT APPEARS THESE MUST BE MISPRINTS. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|