Plan Review Notes
Plan Review Notes For Permit 03072014
Permit Number 03072014
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-01 00:00:00********** UNSAT ********************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE
 INFORMATION ON TITLE BLOCK AS REQ'D
 UNDER FS-471, 61G15-23.004.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 SERVICE TO BE NEW? NO NOTES IF ALL
 EXISTING?
  
 3)NOTE: PLEASE SEE ALL SERVICE CONDUCTOR
 -S.??350MCM FOR 600A'S, #1'S FOR 200A
 MAIN DISC'S? PLEASE SIZE AND SHOW PER
 310.16
 350MCM MENTIONS IN ONE 3' CONDCUIT? IS
 THIS MEANT TO BE 2-3" CONDUITS?
  
 IT APPEARS THESE MUST BE MISPRINTS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  