Plan Review Notes
Plan Review Notes For Permit 03071965
Permit Number 03071965
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-18 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE HOW ACCESS TO ATTIC WILL BE
 PROVIDED AS REQUIRED BY FBC 2309.6.
  
 3) FBC 1707.4.4.2 REQUIRES THAT THE 1X
 BUCK EXTEND PAST THE INTERIOR FACE OF
 THE FRAME TO PROVIDE FULL SUPPORT.PLEASE
 REVISE WINDOW BUCK DETAIL A ON A2.
  
 4) FBC 1609.4.3 NO LONGER ALLOWS THE
 ONE-THIRD INCREASE IN THE STEEL
 CALCULATIONS. PLEASE REVISE THE TRUSS
 ANCHOR SCHEDULE ON A3 TO VALUES THAT DO
 NOT INCLUDE THIS INCREASE. SEE THE 2003
 "USP" CATALOG.
  
 5) THE POSITIVE AND NEGATIVE WINDLOAD
 PRESSURES ARE NOT SPECIFIED ON THE PLAN
 FOR THE BRKFST ROOM WINDOWS AND THE
 SLIDING GLASS DOOR IN THE FAMILY ROOM.
  
 6) PROVIDE A LINTEL SCHEDULE.
  
 7) THE GLASS BLOCK AT THE MASTER BATH
 TUB IS IN A HAZARDOUS LOCATION AND IS
 REQUIRED TO HAVE A MINIMUM UNIFORM FACE
 THICKNESS ON 0.25" PER FBC 2405.2.2.
 PLEASE SPECIFY THIS ON PLANS.
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM. FBC 13-103
  
 9) THE PRODUCT APPROVAL FOR THE SLIDING
 GLASS DOOR IS FOR THE OXXO CONFIGURATION
 ONLY AND DOES NOT COVER THE TWO PANEL
 DOOR SHOWN ON THE PLANS. PLEASE SUBMIT
 THE APPROPRIATE PRODUCT APPROVAL.
  
 10) PLEASE SUBMIT LEGIBLE COPIES OF THE
 PRODUCT APPROVALS FOR THE GLASS BLOCK.
  
 11) PLEASE SUBMIT MANUFACTURER'S SPECS.
 AND UL LISTING INFORMATION FOR THE GAS
 BBQ.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714