Plan Review Notes
Plan Review Notes For Permit 03071940
Permit Number 03071940
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-11 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03071940
 ADD: 4200 BEAR LAKES COURT
 CONT: ALLIANCE CONSTRUCTION
 TEL: (305)345-2029
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 DUMPSTER
 ACTION: DENIED
  
 1)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 2)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 3)11-4.8.3. CLEAR WIDTH. THE MINIMUM
 CLEAR WIDTH OF A RAMP SHALL BE 36".
 EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
  
 4)11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60".
  
 5)11-4.3.3 WIDTH. THE MINIMUM CLEAR
 WIDTH OF AN ACCESSIBLE ROUTE SHALL BE
 36" EXCEPT AT DOORS. IF A PERSON IN A
 WHEELCHAIR MUST TURN AROUND AN OBSTRUC-
 TION, THE MINIMUM CLEAR WIDTH OF THE
 ACCESSIBLE ROUTE SHALL BE SHOWN IN
 FIGURE 7(A) AND (B).FL ACCESSIBILITY
  
  
 6) 11-4.1.3(15) DETECTABLE WARNING AS
 11-4.29.2 (1)(2) SEE ANSI 117.705.1
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026