Plan Review Notes
Plan Review Notes For Permit 03071938
Permit Number 03071938
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03071938
 ADD: 4065 N HAVERHILL ROAD
 CONT: RIGNICK CONSTRUCTION
 TEL: (954)931-6896
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) ADDRESS ON THE PERMIT APPLICATION
 DOES NOT MEET THE U. S. POSTAL REGULA-
 TIONS. NO SUITE "B" ALPHA CHARACTERS
 NOT ALLOWED IN THE POSTAL STANDARD.
  
 2)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) WINDOWS-LARGE MISSLE IMPACT RESISTANT
 B) DOORS-LARGE MISSLE IMPACT RESISTANT
 C) 2'-5" DOOR NOTE# 5 DEMO PLAN?
  
 5) TABLE 1004 BUSINESS: MINIMUM CLEAR
 OPENING OF EXIT DOORS 32", WHY IS DOOR
 NOTE# 5 DEMO PLAN 2'-5"?
  
 6) FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 2405.2.1(3)GLAZING WITHIN 24" OF A SWING
 DOOR, LATCH SIDE, & WHOSE BOTTOM EDGE IS
 LESS THAN 60" ABOVE THE FLOOR OR WALKING
 SURFACE.
  
 7)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 8)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026