Plan Review Notes
Plan Review Notes For Permit 03071916
Permit Number 03071916
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-19 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE INSTALLATION SCHEDULE FOR
 STORM SHUTTERS. REVISE THE ANCHOR
 SPACING FOR WOOD ANCHORS. SEE THE
 ENGINEERED DRAWINGS FOR MAXIMUM
 ANCHOR SPACING ALLOWED AND REVISE AS
 REQUIRED.
 2-RESUBMIT ENERGY CALCULATIONS WITH
 THE ENGINEER'S ORIGINAL SEAL,
 SIGNATURE AND SEAL AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 3-RESUBMIT SOIL TEST REPORT WITH
 ORIGINAL SEAL, SIGNATURE, DATE.
 CHAPTER 471 FLORIDA STATUTES.