| 2003-08-11 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03071836 |
| | ADD: 326 ACACIA RD |
| | CONT: BRICE BUILDING |
| | TEL: (954)420-0110 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) WHAT TYPE BUILDING IS THIS? |
| | |
| | 2) PLANS INDICATE THAT THIS SPACE WILL |
| | BE USED FOR DANCE STUDIO BUT THE OCCUPAN |
| | CY INDICATED IS BUSINESS? EDUCATION. |
| | |
| | 3) TOTAL OCCUPANT LOAD IS INDICATED AS |
| | 75, THIS REQUIRES 2 MEANS OF EGRESS SEE |
| | 1004.1.2. |
| | THE 2 MEANS OF EGRESS SHALL BE AT LEAST |
| | 1/3RD THE DISTANCE APART FOR FULLY SPRIN |
| | KLERED BUILDINGS. |
| | |
| | 4) RAMPS @ ENTRY DOOR # 418, |
| | 11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| | ON RAMPS SHALL NOT BE LESS THAN 60" |
| | CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| | HAVE NOT LESS THAN 72" OF STRAIGHT & |
| | LEVEL CLEARENCE.ALSO SEE 1012.3 MOST |
| | RESTRICTIVE SHALL APPLY. |
| | |
| | 5)11-4.1.3(3) GROUND & FLOOR SURFACES |
| | ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| | ROOMS & SPACES SHALL COMPLY WITH |
| | 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| | A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| | IS RECOMENDED FOR ACCESSIBLE ROUTES |
| | AND 0.8 FOR RAMPS. |
| | |
| | THE NEW EGRESS DOORWAY TO COMPLY WITH |
| | 1021.4. |
| | |
| | 6) DEPENDING ON THE TYPE BUILDING THIS |
| | BUILDING IS THIS COMMENT MAY OR MAY NOT |
| | APPLY, SEE 803.7 FLOOR FINISHES. |
| | |
| | |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |