Plan Review Notes
Plan Review Notes For Permit 03071724
Permit Number 03071724
Review Stop P
Sequence Number 2
Notes
Date Text
2003-09-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 A) PIPE SIZE NOT CORRECT. 1-1/2" TO W/M
 NOT APPROVED. ANY PORTION OF THE DRAIN-
 AGE SYSTEM INSTALLED UNDERGROUND SHALL
 NOT BE LESS THAN 2" IN DIAMETER. SECTION
 710.3. - THE SIZE OF THE DRAINAGE PIPING
 SHALL NOT BE REDUCED IN THE DIRECTION OF
 THE FLOW. SECTION 704.2 (W/M SHOWN FROM
 2" PIPE TO 1-1/2").
 B) 2ND FLOOR BATHROOM STILL DRAIN THRU
 THE DRAINAGE PIPING FOR THE FIRST FLOOR
 BATHROOM. THIS IS NOT ALLOWED. SECTION
 908.2.
 C) STANDPIPE REQUIRED AT WASH MACHINE
 SECTION 802.4
 D) CLEANOUT REQUIRED 4' ABOVE FLOOR AT
 WASH MACHINE. SECTION 708.10
 E) W/C AND SHOWER ARE NOT VENTED AT
 FIRST FLOOR BATHROOM. SECTION 901.2.1
 2) SHOWER ON SANITARY RISER DIAGRAM IS
 LABELED AS A FLOOR DRAIN.
 3) SEE RED LINE CORRECTIONS FROM THE 1ST
 REVIEW FOR A SANITARY RISER DIAGRAM THAT
 MEETS CODE REQUIREMENTS.
 4) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B).
 ********WHEN RESUBMITTING PLANS*********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS