| 2003-09-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FLORIDA STATUTES |
| | |
| | 1) SANITARY RISER DIAGRAM DOES NOT MEET |
| | CODE REQUIREMENTS. |
| | A) PIPE SIZE NOT CORRECT. 1-1/2" TO W/M |
| | NOT APPROVED. ANY PORTION OF THE DRAIN- |
| | AGE SYSTEM INSTALLED UNDERGROUND SHALL |
| | NOT BE LESS THAN 2" IN DIAMETER. SECTION |
| | 710.3. - THE SIZE OF THE DRAINAGE PIPING |
| | SHALL NOT BE REDUCED IN THE DIRECTION OF |
| | THE FLOW. SECTION 704.2 (W/M SHOWN FROM |
| | 2" PIPE TO 1-1/2"). |
| | B) 2ND FLOOR BATHROOM STILL DRAIN THRU |
| | THE DRAINAGE PIPING FOR THE FIRST FLOOR |
| | BATHROOM. THIS IS NOT ALLOWED. SECTION |
| | 908.2. |
| | C) STANDPIPE REQUIRED AT WASH MACHINE |
| | SECTION 802.4 |
| | D) CLEANOUT REQUIRED 4' ABOVE FLOOR AT |
| | WASH MACHINE. SECTION 708.10 |
| | E) W/C AND SHOWER ARE NOT VENTED AT |
| | FIRST FLOOR BATHROOM. SECTION 901.2.1 |
| | 2) SHOWER ON SANITARY RISER DIAGRAM IS |
| | LABELED AS A FLOOR DRAIN. |
| | 3) SEE RED LINE CORRECTIONS FROM THE 1ST |
| | REVIEW FOR A SANITARY RISER DIAGRAM THAT |
| | MEETS CODE REQUIREMENTS. |
| | 4) SEE ATTACHED SHEET CONCERNING FLORIDA |
| | STATUTE 553.80(2)(B). |
| | ********WHEN RESUBMITTING PLANS********* |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. |
| | |