Plan Review Notes
Plan Review Notes For Permit 03071724
Permit Number 03071724
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CORRECTIONS
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE PANEL SCHEDULE INDICATES PANEL
 "A" IS A 200 AMP MLO,THE RISER SHOWS
 PANEL "A" AS 150 AMP WITH A MAIN
 BREAKER.PLEASE CORRELATE.
  
 3} THE PANEL SCHEDULE SHOWS 2 SMALL
 APPLIANCE CIRCUITS,EACH ON A SINGLE
 POLE 20 WITH A LOAD OF 3KW,ON
 #12 WIRE.PLEASE CORRECT.
  
 4} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH ALL OF ARTICLE 250 THAT ARE
 AVAILABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718