| Plan Review Notes For Permit 03071724 |
| Permit Number |
03071724 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-04 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CORRECTIONS | | | ON THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} THE PANEL SCHEDULE INDICATES PANEL | | | "A" IS A 200 AMP MLO,THE RISER SHOWS | | | PANEL "A" AS 150 AMP WITH A MAIN | | | BREAKER.PLEASE CORRELATE. | | | | | | 3} THE PANEL SCHEDULE SHOWS 2 SMALL | | | APPLIANCE CIRCUITS,EACH ON A SINGLE | | | POLE 20 WITH A LOAD OF 3KW,ON | | | #12 WIRE.PLEASE CORRECT. | | | | | | 4} THE GROUNDING ELECTRODE SYSTEM MUST | | | COMPLY WITH ALL OF ARTICLE 250 THAT ARE | | | AVAILABLE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|