| 2003-09-16 00:00:00 | ******CORRECTIONS******** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025. |
| | |
| | 2.)TWO COPIES OF THE ENERGY CALCS |
| | MUST BE PROVIDED. |
| | |
| | 3.)ENERGY CALC, PRESCRIPTIVE METHOD |
| | C, REQUIRES R30 MINIMUM INSULATION IN |
| | THE UNDER ATTIC SPACE.YOU SPECIFY R19 |
| | ON THE ENERGY CALC (SEE THE BACK OF THE |
| | FORM FOR THE MINIMUM INSULATION). |
| | HOWEVER, THE ENTRY SECTION SHOWS THIS |
| | AREA AS A SINGLE ASSEMBLY.EITHER |
| | CHANGE THE ENERGY CALC TO REFLECT THE |
| | SINGLE ASSEMBLY OR CHANGE THE R19 TO |
| | R30 UNDER ATTIC AND REVISE A-8.1. |
| | |
| | 4.)A PRODUCT APPROVAL IS REQUIRED FOR |
| | THE FRONT DOOR.THE PERMIT WILL BE |
| | ISSUED WITH A PROVISO TO SUBMITTHE |
| | PRODUCT APPROVAL BEFORE INSTALLATION. |
| | |
| | 5.)A-8.1, NEW 2X10 FLOOR JOISTS, MUST |
| | COMPLY WITH FBC2304.3.4. |
| | |
| | 6.)SIMPSON LU210 JOIST HANGER IS A |
| | WOOD-TO-WOOD CONNECTOR.A-8.1 SHOWS |
| | IT IN A MASONRY APPLICATION. |
| | |
| | 7.)THE REVISED SHEETS MUST BE STAMPED |
| | BY THE HISTORIC PRESERVATION DEPARTMENT. |