Plan Review Notes
Plan Review Notes For Permit 03071724
Permit Number 03071724
Review Stop B
Sequence Number 2
Notes
Date Text
2003-09-16 00:00:00******CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025.
  
 2.)TWO COPIES OF THE ENERGY CALCS
 MUST BE PROVIDED.
  
 3.)ENERGY CALC, PRESCRIPTIVE METHOD
 C, REQUIRES R30 MINIMUM INSULATION IN
 THE UNDER ATTIC SPACE.YOU SPECIFY R19
 ON THE ENERGY CALC (SEE THE BACK OF THE
 FORM FOR THE MINIMUM INSULATION).
 HOWEVER, THE ENTRY SECTION SHOWS THIS
 AREA AS A SINGLE ASSEMBLY.EITHER
 CHANGE THE ENERGY CALC TO REFLECT THE
 SINGLE ASSEMBLY OR CHANGE THE R19 TO
 R30 UNDER ATTIC AND REVISE A-8.1.
  
 4.)A PRODUCT APPROVAL IS REQUIRED FOR
 THE FRONT DOOR.THE PERMIT WILL BE
 ISSUED WITH A PROVISO TO SUBMITTHE
 PRODUCT APPROVAL BEFORE INSTALLATION.
  
 5.)A-8.1, NEW 2X10 FLOOR JOISTS, MUST
 COMPLY WITH FBC2304.3.4.
  
 6.)SIMPSON LU210 JOIST HANGER IS A
 WOOD-TO-WOOD CONNECTOR.A-8.1 SHOWS
 IT IN A MASONRY APPLICATION.
  
 7.)THE REVISED SHEETS MUST BE STAMPED
 BY THE HISTORIC PRESERVATION DEPARTMENT.