| Plan Review Notes For Permit 03071724 |
| Permit Number |
03071724 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. | | | A) PIPE SIZES NOT CORRECT. 3" MINIMUM | | | FOR WATER CLOSETS. TABLE 709.1 | | | B) 2" MINIMUM FOR ALL PIPING FOR SHOWER | | | UNDERGROUND. SECTION 710.3 | | | C) 2ND FLOOR BATHROOM FIXTURES SHALL | | | NOT DRAIN IN VENT FOR 1ST FLOOR BATHROOM | | | SECTION 908.3 | | | D) LAV IN 1ST FLOOR BATHROOM NOT VENTED | | | E) WASHMACHINE NOT VENTED PROPERLY. 2" | | | STANDPIPE REQUIRED. CLEANOUT REQUIRED 4' | | | ABOVE FLOOR. | | | 2) SEE RED LINE CORRECTIONS FOR PIPE | | | SIZES AND ROUTING OF PIPING. CHANGE TO | | | MEET CODE REQUIREMENTS AND RESUBMIT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|