Plan Review Notes
Plan Review Notes For Permit 03071724
Permit Number 03071724
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 A) PIPE SIZES NOT CORRECT. 3" MINIMUM
 FOR WATER CLOSETS. TABLE 709.1
 B) 2" MINIMUM FOR ALL PIPING FOR SHOWER
 UNDERGROUND. SECTION 710.3
 C) 2ND FLOOR BATHROOM FIXTURES SHALL
 NOT DRAIN IN VENT FOR 1ST FLOOR BATHROOM
 SECTION 908.3
 D) LAV IN 1ST FLOOR BATHROOM NOT VENTED
 E) WASHMACHINE NOT VENTED PROPERLY. 2"
 STANDPIPE REQUIRED. CLEANOUT REQUIRED 4'
 ABOVE FLOOR.
 2) SEE RED LINE CORRECTIONS FOR PIPE
 SIZES AND ROUTING OF PIPING. CHANGE TO
 MEET CODE REQUIREMENTS AND RESUBMIT.
  