| 2003-08-12 00:00:00 | *****CORRECTIONS****** |
| | |
| | 1.) SHEET 4.1, NOTES, REFERS TO FBC2000. |
| | SHOULD BE FBC2001. |
| | |
| | 2.) ARE THE WINDOWS AT THE 2ND FLOOR |
| | BEDROOM TO BE REPLACED?IF THEY ARE, |
| | SHOW SIZE TO SHOW COMPLIANCE WITH |
| | FBC1005.4 (EGRESS).IF NOT, INDICATE |
| | AS EXISTING. |
| | |
| | 3.)SHEET 4.1 REFERS TO SHEETS A17 |
| | AND 9.1 (TYPICAL WOOD BUCK TO CONCRETE). |
| | SHEETS REFERRED TO ARE NOT A PART OF THE |
| | PLAN. |
| | |
| | 4.)2ND FLOOR FRAMING PLAN APPEARS TO |
| | BE THE 1ST FLOOR. |
| | |
| | 5.)A PRODUCT APPROVAL IS REQUIRED FOR |
| | THE FRONT DOOR.IF A TEST REPORT IS NOT |
| | AVAILABLE, YOU MAY SUBMIT A SITE |
| | SPECIFIC.THIS CAN BE SUBMITTED NOW |
| | OR THE PERMIT CAN BE ISSUED WITH A |
| | PROVISO THAT THE PRODUCT APPROVAL FOR |
| | THE FRONT DOOR BE SUBMITTED BEFORE |
| | INSTALLATION. |
| | |
| | 6.)SEPARATE PERMITS REQUIRED FOR THE |
| | ROOF.SUBMIT PRODUCT APPROVAL WITH THE |
| | ROOF PERMIT APPLICATION. |
| | |
| | 7.)AREA CALCULATIONS SHOULD SHOW |
| | EXISTING, PROPOSED, AND A NEW TOTAL. |
| | |
| | 8.)ENERGY CALCS REQUIRED FBC13-101.2, |
| | UNLESS THIS IS A CONTRIBUTORY PROPERTY |
| | (HISTORIC) AS PER FBC3401.5. |
| | |
| | 9.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |