Plan Review Notes
Plan Review Notes For Permit 03071724
Permit Number 03071724
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-12 00:00:00*****CORRECTIONS******
  
 1.) SHEET 4.1, NOTES, REFERS TO FBC2000.
 SHOULD BE FBC2001.
  
 2.) ARE THE WINDOWS AT THE 2ND FLOOR
 BEDROOM TO BE REPLACED?IF THEY ARE,
 SHOW SIZE TO SHOW COMPLIANCE WITH
 FBC1005.4 (EGRESS).IF NOT, INDICATE
 AS EXISTING.
  
 3.)SHEET 4.1 REFERS TO SHEETS A17
 AND 9.1 (TYPICAL WOOD BUCK TO CONCRETE).
 SHEETS REFERRED TO ARE NOT A PART OF THE
 PLAN.
  
 4.)2ND FLOOR FRAMING PLAN APPEARS TO
 BE THE 1ST FLOOR.
  
 5.)A PRODUCT APPROVAL IS REQUIRED FOR
 THE FRONT DOOR.IF A TEST REPORT IS NOT
 AVAILABLE, YOU MAY SUBMIT A SITE
 SPECIFIC.THIS CAN BE SUBMITTED NOW
 OR THE PERMIT CAN BE ISSUED WITH A
 PROVISO THAT THE PRODUCT APPROVAL FOR
 THE FRONT DOOR BE SUBMITTED BEFORE
 INSTALLATION.
  
 6.)SEPARATE PERMITS REQUIRED FOR THE
 ROOF.SUBMIT PRODUCT APPROVAL WITH THE
 ROOF PERMIT APPLICATION.
  
 7.)AREA CALCULATIONS SHOULD SHOW
 EXISTING, PROPOSED, AND A NEW TOTAL.
  
 8.)ENERGY CALCS REQUIRED FBC13-101.2,
 UNLESS THIS IS A CONTRIBUTORY PROPERTY
 (HISTORIC) AS PER FBC3401.5.
  
 9.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]