| Date |
Text |
| 2003-08-15 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT A FINAL SOIL TEST REPORT AS |
| | REQUIRED BY THE PRELIMINARY SOIL REPORT |
| | AND FBC 1804.2.2. |
| | |
| | 3) THE STRUCTURE IS LOCATED IN AN "AO" |
| | FLOD ZONE AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED. |
| | |
| | 4) REVISE NOTE #11 UNDER PLAN NOTES ON |
| | C1. FBC 1606.1.4 REQUIRES PROTECTION OF |
| | GLAZED OPENINGS IN WINDBOURNE DEBRIS |
| | REGIONS AS WELL AS THE HVHZ. |
| | |
| | 5) REVISE NOTE #15 UNDER FRAMING NOTES |
| | ON C1. ASTM C 1063 REQUIRES HIGH RIB |
| | METAL LATH TO BE ATTACHED AT EACH RIB |
| | (4"O.C.). |
| | |
| | 6) THE ENERGY CALCS. ARE REQUIRED TO BE |
| | SIGNED BY THE OWNER/AGENT. SEE FBC |
| | CHAPTER 13. |
| | |
| | 7) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | 1/2" DIA. A.B. FOR THE GARAGE DOOR BUCK |
| | ON A4. |
| | |
| | 8) CLARIFY ON THE BUCK DETAIL FOR THE |
| | SLIDING GLASS DOOR ON A4 THAT THE FRAME |
| | IS FASTENED THROUGH THE 1X BUCK. SEE |
| | FBC 1707.4.4.2. |
| | |
| | 9) DETAIL 6 ON A5 SPECIFIES A HANGER |
| | WITH THROUGH BOLTS AT A BLOCK WALL. |
| | PLEASE CLARIFY. |
| | |
| | 10) THE GLASS BLOCK OPENINGS IN THE |
| | MASTER BATH ARE IN HAZARDOUS LOCATIONS |
| | AND ARE REQUIRED TO BE TEMPERED OR HAVE |
| | A MINIMUM UNIFORM FACE THICKNESS OF |
| | 0.25" PER FBC 2405.2.2. PLEASE SPECIFY |
| | ON THE PLANS. |
| | |
| | 11) THE BUILDING SET BACKS ON THE SITE |
| | PLAN S-1 AND THE SURVEY DIFFER. PLEASE |
| | CORRECT. |
| | |
| | 12) SUBMIT THE CLEAR OPENING DIMENSIONS |
| | AND AREA FROM THE MANUFACTURER FOR THE |
| | SH 24-4 EGRESS WINDOWS. |
| | |
| | 13) THE TAG FOR DETAIL 3 ON A5 IS SHOWN |
| | ON THE FRAMING PLAN IN THE WRONG |
| | LOCATION. |
| | |
| | 14) FBC 1609.4.3 DOES NOT ALLOW THE ONE- |
| | THIRD INCREASE IN THE STEEL CALCULATIONS |
| | FOR COMBINED LOADS. PLEASE REVISE THE |
| | DETAILS ON A5 AND THE TRUSS CONNECTOR |
| | SCHEDULE ON A6 TO VALUES THAT DO NOT |
| | INCLUDE THIS INCREASE. SEE THE 2003 USP |
| | CATALOG. |
| | |
| | 15) THE SITE SPECIFIC PRODUCT APPROVAL |
| | LETTER FROM SCOTT DISHER DOES NOT |
| | INDICATE THE LOT NUMBER. |
| | |
| | 16) THE SITE SPECIFIC ENGINEERING FOR |
| | THE FIXED GLASS WINDOWS DOES NOT HAVE |
| | THE 74"X 96" F.G.WINDOW AT THE LIVING |
| | ROOM OR THE 18" DIAMETER F.G. WINDOW IN |
| | BATH 2. |
| | |
| | 17) THE 37"X 24" FIXED GLASS WINDOW IN |
| | THE FAMILY ROOM THAT IS IN THE END ZONE |
| | EXCEEDS THE DESIGN PRESSURES LISTED IN |
| | THE SITE SPECIFIC ENGINEERING. |
| | |
| | 18) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SINGLE HUNG WINDOWS |
| | - STRUCTURAL MULLIONS (CONNECTING THE |
| | (2) 35SH WINDOWS AT THE MASTER SUITE) |
| | |
| | 19) THE FRONT ELEVATION LISTS THE WRONG |
| | SIZE M.O. FOR THE WINDOW IN BEDROOM 4. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |