Plan Review Notes
Plan Review Notes For Permit 03071511
Permit Number 03071511
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-07 00:00:00********** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES.
 A/C SUB PANEL IS SHOWN AS AN 80A FEED
 AND AWG IS ONLY RATED FOR 60A'S. A/C
 PANEL IS SHOWN AS 60A ON RISER?
  
 2)NOTE: PLEASE SEE THE ONLY PANEL
 SCHEDULE SUBMITTED FOR A SUB PANEL IS
 FOR A 125A GEN LT AND RECEPTS.
 PLEASE SUBMIT OTHER PANEL SCHEDULES AS
 REQ'D. 215.5
  
 3)NOTE: PLEASE SEE THAT A NEW RISER IS
 NOW SUBMITTED. PLEASE SEE MISSING FOOTER
 STEEL AND COLD WATER PIPE REQD FOR
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 4)NOTE: PLEASE SEE 210.12 ARC FAULT IS
 NOT FOR ONLY RECEPTS UNDER THE 2002 NEC
 WHICH WENT INTO EFFECT 7/1/2003
  
 5)NOTE: PLEASE SEE THAT LOAD FOR A/C
 SUB PANEL IS SHOWN AT 75A'S.
  
 6)NOTE: RANGE IS SHOWN AS OPT (GAS) A
 MIN LOAD FOR ELECTRICAL MUST BE SHOWN
 PER TABLES IN NEC 220
  
 7)NOTE: PLEASE SEE MIN LOAD FOR ELEC
 DRYER TO BE 5KW 220.18
  
 8)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]