Plan Review Notes
Plan Review Notes For Permit 03071511
Permit Number 03071511
Review Stop B
Sequence Number 2
Notes
Date Text
2003-10-10 00:00:00DENIED
  
 1) SHEET RF-1 IS THE REVERSE OF THE REST
 OF THE PLANS. SUBMIT RF-1 SHEET WITH THE
 CORRECT ORIENTATION.
  
 2) SHEETS 1, SD1, SD2, AND RF 1 FOR THE
 ROYALL WALL SYSTEM DOES NOT HAVE THE
 ORIGINAL WET SIGNATURE OF THE ENGINEER
 AS REQUIRED BY FAC 61G15-23.002.
  
 3) IF USING ALLOWABLE STRESS DESIGN,
 INCREASES IN THE ALLOWABLE STRESS OF THE
 STEEL FOR THE TRUSS CONNECTORS IS NOT
 ALLOWED BY FBC 1609.4.3 (2). DESIGN
 CALCULATIONS WILL BE REQUIRED TO BE
 SUBMITTED IF CONNECTOR VALUES WITH THE
 ONE-THIRD INCREASE IS USED.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE
 IMPACT RESISTANT WINDOW IN THE DEN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714