Plan Review Notes
Plan Review Notes For Permit 03071511
Permit Number 03071511
Review Stop E
Sequence Number 1
Notes
Date Text
2003-07-31 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN AT MCB PANEL. NOTES MENTION USE OF
 FUSES AND FUSIBLE DISC HAS BEEN REMOVED?
 110.9
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 AND RISER DIAGRAM. MAIN PANEL SHOWS
 3-SUB PANELS AND ONLY ONE SHOWN ON
 RISER.
  
 4)NOTE: PLEASE SHOW WHERE A/C UNITS ARE
 BEING FED FROM. SHOWS A A/C SUB PANEL
 BUT ONLY SUB PANEL SHOWN IS FEEDING ALL
 GENERAL PURPOSE LT/RECEPTS?
  
 5)NOTE; PLEASE SHOW PANEL LOCATIONS ON
 PLANS.
  
 6)NOTE: PLEASE SEE FAC/ FS 481 AND
 61G1-16.004 FOR MISSING INFORMATION
 RE'D ON TITLE BLOCK FOR ARCH OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]