| Plan Review Notes For Permit 03071511 |
| Permit Number |
03071511 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-31 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | MAIN AT MCB PANEL. NOTES MENTION USE OF | | | FUSES AND FUSIBLE DISC HAS BEEN REMOVED? | | | 110.9 | | | | | | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES | | | AND RISER DIAGRAM. MAIN PANEL SHOWS | | | 3-SUB PANELS AND ONLY ONE SHOWN ON | | | RISER. | | | | | | 4)NOTE: PLEASE SHOW WHERE A/C UNITS ARE | | | BEING FED FROM. SHOWS A A/C SUB PANEL | | | BUT ONLY SUB PANEL SHOWN IS FEEDING ALL | | | GENERAL PURPOSE LT/RECEPTS? | | | | | | 5)NOTE; PLEASE SHOW PANEL LOCATIONS ON | | | PLANS. | | | | | | 6)NOTE: PLEASE SEE FAC/ FS 481 AND | | | 61G1-16.004 FOR MISSING INFORMATION | | | RE'D ON TITLE BLOCK FOR ARCH OF RECORD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|