Plan Review Notes
Plan Review Notes For Permit 03071511
Permit Number 03071511
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-15 00:00:00DENIED
  
 1) THE ENGINEER'S TITLE BLOCK DOES NOT
 HAVE HIS LICENSE NUMBER LISTED. THE
 TITLE BLOCK ON THE PLANS AND THE ROYAL
 WALL DRAWINGS ARE DIFFERENT FOR THE SAME
 ENGINEER. PLEASE CLARIFY. THE REGISTRAT-
 ION NUMBER FOR THE ENGINEERING FIRM IS
 REQUIRED IN THE TITLE BLOCK. SEE FAC
 61G15-23002.
  
 2) THE TITLE BLOCK FOR THE ARCHITECT IS
 MISSING THE ADDRESS AND LICENSE NUMBER.
 SEE FAC 61G1-16.004.
  
 3) AFFINITY ARCHITECTS SHOULD REMOVE
 THEIR TITLE BLOCK IF THEY ARE NOT THE
 DESIGNERS OF RECORD.
  
 4) SHEET 2 REFERENCES THE 1997 STANDARD
 GAS CODE. PLEASE UPDATE TO THE 2001 FBC
 FUEL GAS CODE.
  
 5) THE TOTAL SQFT LISTED ON SHEET 2 IS
 INCORRECT. PLEASE RETOTAL AREAS LISTED.
  
 6) FBC 11-4.23.2 REQUIRES AT LEAST ONE
 BATH ROOM WITH A DOOR THAT HAS A 29"
 CLEAR OPENING. BECAUSE FULL BATHS ARE
 PROVIDED ON HABITABLE GRADE, ONE OF THEM
 MUST COMPLY.
  
 7) SHEET 6 SPECIFIES HUGHES CONNECTORS
 ON THE KNEE WALL AND INTERIOR BEARING
 PARTITION DETAILS. HUGHES IS NO LONGER
 IN BUSINESS. PLEASE UPDATE.
  
 8) HUGHES ANS SEMCO CONNECTORS ARE
 SPECIFIED ON RF-1. THEY ARE NO LONGER IN
 BUSINESS. PLEASE UPDATE.
  
 9) THE ROOF SHEATHING NAILING ON THE
 TYPICAL WALL SECTION ON SHEET 6 DOES NOT
 CORRESPOND WITH THE NAILING SCHEDULE ON
 SHEET 4. PLEASE CORRECT.
  
 10) FBC 1609.4 DOES NOT ALLOW A ONE-
 THIRD INCREASE IN STEEL STRESS CALCS.
 PLEASE REVIEW THE ANCHOR SCHEDULES ON
 RF-1 AND SD2 AND REVISE VALUES.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
  
 12) THE DOOR FROM THE GARAGE TO THE
 CONDITIONED AREA IS REQUIRED TO BE
 SOLID CORE OR INSULATED. SEE FBC CHAPTER
 13-603.1.ABC.1.
  
 13)STORM PANELS:THE SAFEGUARD COMPANY IS
 NO LONGER IN BUSINESS AND WEATHERGUARD
 HAS NOT COMPLETED THE PROCESS OF
 ASSUMING THE PRODUCT APPROVAL FROM SBCCI
 THE BUILDING OFFICIAL HAS DETERMINED
 THAT WE CAN NOT ACCEPT THIS PRODUCT FOR
 USE IN THE CITY OF WPB AT THIS TIME.
 THE SBCCI REPORT NO. 9808 THAT WAS
 SUBMITTED IS NO LONGER CURRENT.
  
 14)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 PLEASE INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 15) THE TRUSS DRAWINGS FOR SINGLE FAMILY
 DWELLINGS ARE NO LONGER REQUIRED TO BE
 SUBMITTED FOR PLAN REVIEW. THEY ARE TO
 BE GIVEN TO THE INSPECTOR AT THE ROOF
 FRAMING INSPECTION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714