| 2003-08-26 00:00:00 | **************UNSAT *************** |
| | |
| | PLEASE SEE NOTES FROM FIRST REVIEW, SOME |
| | NOT COMPLETED.SOME NEW NOTES FROM PLANS |
| | BEING CHANGED AND FROM RISER DIAGRAM |
| | BEING SUBMITTED. |
| | |
| | 1)NOTE: PLEASE CLARIFY SIZING OF SERVICE |
| | ENT CONDUCTORS FOR 200A SERVICE. SHOWN |
| | AS 1/0`S PLEASE SEE 310.16. |
| | |
| | 2)NOTE: PLEASE CLARIFY HOW SUB PANEL IS |
| | BEING FED? RISER SHOWS COMING FROM PANEL |
| | 'A', YET PANEL "A" SCHEDULE DOES NOT |
| | SHOW SUB PANEL/OCP FEEDING PANEL "B"?? |
| | |
| | 3)NOTE: PLEASE CLARIFY TWO ITEMS SHOWN |
| | ON PANEL SCHEDULE "A" ,220A CIRCUIT? |
| | ONE SHOWN WITH #10 AWG? PLEASE CLARIFY |
| | WHAT THESE ARE? |
| | |
| | 4)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLAN W/ PANEL SCHEDULE. PLEASE SEE |
| | WATER HEATER?WH, SHOWN AS #6, YET |
| | PANEL SCHEDULE SHOWS GEN LTS? |
| | |
| | 5)NOTE: PLEASE SEE 250.110 AND 250.122 |
| | FOR MISSING EQUIPMENT GROUNDING CONDUCT- |
| | OR FROM MAIN PANEL TO SUB-PANEL? |
| | |
| | 6)NOTE: PLEASE SEE 424.3B FOR SIZING |
| | OF OCP FOR AHU. PLEASE ALSO SEE 310.16 |
| | FOR AWG. |
| | |
| | 7)NOTE: PLEASE SEE 210.8B, 1,2,3 FOR |
| | GFI PROTECTION REQ'D IN KITCHENS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |