| Plan Review Notes For Permit 03071487 |
| Permit Number |
03071487 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-23 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE CLARIFY CONFLICTING NOTES | | | ON PLANS. NOTE 6 MENTIONS TO CONNECT | | | NEW ELEC TO EXISITNG PANELS, HOWEVER | | | OTHER NOTES MENTION THAT BOTH PANELS | | | ARE BEING REPLACED? | | | PLEASE CORRELATE. | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE W/ A SUBMITTED PANEL | | | SCHEDULE. | | | PLEASE CIRCUIT EM/EXT LTS PER 700.12E | | | | | | 3)NOTE: PLEASE CLARIFY NEW/OR EXISTING | | | EGRESS LIGHTING OUTSIDE DOORWAYS. | | | LIFE SAFETY 101 5-8 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|