| Plan Review Notes For Permit 03071467 |
| Permit Number |
03071467 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-09 00:00:00 | PROVISO: | | | | | | 1.PLAN SHEET 2 SECTION VIEW OF THE | | | HOOD, EXHAUST FAN TERMINATION SHALL | | | COMPLY WITH 2001 FBC(M) 506.3.14.3 | | | EXCEPTION #2, THE MINIMUM HORIZONTAL | | | DISTANCE BETWEEN VERTICAL DISCHARGE FANS | | | AND PARAPET-TYPE BUILDING STRUCTURES | | | SHALL BE TWO FEET PROVIDED THAT SUCH | | | STRUCTURES ARE NOT HIGHER THAN THE TOP | | | OF THE FAN DISCHARGE OPENING. | | | | | | 2.PROVIDE INSTALLATION INSTRCTIONS FOR | | | THE 2 HR FIRE WRAP ON THE JOBSITE AT THE | | | TIME OF INSPECTION. | | | | | | 3.ADDITIONAL PLANS AND PERMIT REQUIRED | | | FOR THE FIRE SUPPRESSION. | | | | | | 4.ADDITIONAL PERMIT REQUIRED SHOULD | | | THE WALK-IN COOLER BE NEW.PLEASE | | | PROVIDE MANUFACTURER CUT SHEETS WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|