| Plan Review Notes For Permit 03071461 |
| Permit Number |
03071461 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FLORIDA STATUTES | | | | | | 1) SHT 3 FLOOR SINK UNDER 6-BURNER WITH | | | OVEN. INDICATE WHAT DRAINS INTO THIS | | | FLOOR SINK. IF IT IS A FLOOR DRAIN IT | | | SHALL BE LOCATED WHERE IT CAN BE SERV- | | | ICED. 412.2 | | | 2) COVER SHEET STILL SHOWS A DEMO PLAN | | | D-1. THIS SHEET STILL NOT FOUND. PLEASE | | | CLAIRFY. 104.2.1 | | | 3) SHOW ALL PIPE SIZES FOR GAS LINES. | | | NOT ADDRESSED FROM PREVIOUS REVIEW. | | | 4) ALL GAS APPLIANCE MANUFACTURE SHEETS | | | NOT SUBMITTED. RICE COOKERS NOT SUBMITT- | | | ED. FRYERS MANUF. SHEETS INDICATE 105K | | | BTU, BUT RISER SHOWS 90K. PLEASE CLAIRFY | | | CHARBROILER - RISER SHOWS 120K BTU, GAS | | | CALCULATION CHART SHOWS 90K BTU, AND | | | MANUF. INFORMATION INDIACATES 60K BTU'S | | | PLEASE CLAIRFY. 6 BURNER W/OVEN ON RISER | | | SHOWS 270K BTU, GAS CALCULATION CHART | | | SHOWS 203K BTU, MANUF. INFORMATION DOES | | | NOT CALL OUT WHICH MODEL IS BEING USED. | | | PLEASE CLAIRFY. | | | 5) PLUMBING PERMIT REQUIRED. | | | 6) SEE ATTACHED SHEET CONCERNING FLORIDA | | | STATUTE 553.80(2)(B) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|