| Plan Review Notes For Permit 03071461 |
| Permit Number |
03071461 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) SHT 3 FLOOR SINKS AT 6-BURNER W/OVEN | | | SHALL DRAIN TO GREASE LINE. | | | 2) COVER SHEET SHOWS DEMO PLAN D-1 BUT | | | THIS SHEET NOT FOUND. PLEASE CLAIRFY. | | | 3) ALL CAPPED AND DEMO'ED PIPING SHALL | | | BE INSPECTED PRIOR TO COVERING. | | | 4) SEPARATE GAS PERMIT REQUIRED. | | | 5) SHOW ALL PIPE SIZES FOR GAS LINES. | | | 6) TYPE OF GAS, (LP OR NATURAL) | | | 7) INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 8) SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | 9) GAS RISER DIAGRAM SHOWS 76,000 BTU'S | | | FOR WATER HEATER, BUT GAS CALCULATION | | | CHART SHOW 160,000. PLEASE CLAIRFY. | | | 10) 61G15-23.002(2) CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|