| 2003-10-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FHA-98 DESIGN MANUAL |
| | |
| | A) THE FOLLOWING COMMENTS WERE NOT ADD- |
| | RESSED FROM THE FIRST REVEIW. THE COMM- |
| | ENT NUMBERS SHALL STAY THE SAME FOR |
| | CLAIRITY. |
| | 3) SHT P01 OF 29 FLOOR PLAN FOR A101/S3 |
| | SECOND FLOOR STACK NOT SHOWN ON PLUMBING |
| | LAYOUT. |
| | 7) A.SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). - GAS CHART SHOWS 80,000 BTU'S |
| | FOR NORTH ADDITION, BUT FLOOR PLAN SHOWS |
| | 105,000 BTU'S. PLEASE CLAIRFY. |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | SHOWS .75 PSI. VERIFY WITH GAS PROVIDER. |
| | NORMAL PRESSURE IS EITHER .50 PSI OR |
| | 2 PSI. PLEASE CLAIRFY. |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | NEW COMMENT FOR GAS: |
| | K. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 10) SHT A04 OF 29 UNITS A101, A102, AND |
| | A103 SHALL COMPLY WITH FHA-98 AMENDED |
| | DESIGN MANUAL, REQUIREMENTS 1 THRU 7. |
| | DETAILS SHALL BE SUBMITTED. SHOW ALL |
| | BACKING PER REQ #6. SPECIFICATION "A" OR |
| | "B" BATHROOMS PER REQ. #7B, SHOW CLEAR |
| | FLOOR SPACE FOR ALL BATHROOM FIXTURES & |
| | KITCHEN FIXTURES. SHOW OPENING SIZE FOR |
| | ALL TOILETS, HEIGHTS FOR LAVS. ECT. |
| | |