| 2003-09-24 00:00:00 | *************** UNSAT *************** |
| | |
| | PLEASE SEE THAT MANY COMMENTS FROM |
| | FIRST REVIEW NEED TO BE ADDRESSED FULLY. |
| | |
| | |
| | 1)NOTE: PLEASE SEE SERVICE, PLEASE |
| | CORRELATE PANELS/RISER/ LOAD CALCULATION |
| | -S VOLTAGES ETC. |
| | LOAD CALCS SHOW 120/208V AND SOME PANELS |
| | SHOW 120/240V PLEASE VERIFY VOLTAGE AND |
| | SUBMIT ALL LOAD CALCS/PANEL TO MATCH. |
| | PLEASE CORRELATE RISER. |
| | PLEASE SEE THAT ALL PANELS, INCLUDING |
| | 150A/125A ETC ARE SHOWN AS 42 CIRCUIT |
| | PANELS. PLEASE NOTE, A 125A PANEL IS NOT |
| | MADE FOR 42 CIRCUITS ETC. |
| | PLEASE SEE THAT PANEL 'A' IS SHOWN |
| | FEEDING PANELS B AND C, YET RISER DOES |
| | NOT SHOW THIS? |
| | ETC ETC. |
| | |
| | 2)NOTE: PLEASE SEE 250.50 FOR GROUNDING. |
| | RISER NOTES, GROUND TO FOOTER STEEL OR |
| | COLD WATER OR GAS. PLEASE SEE THAT ALL |
| | OF THESE ARE REQ'D. |
| | |
| | 3)NOTE: PLEASE SEE COMMENT ABOUT SD`S |
| | ON FIRST REVIEW. THIS COMMENT WAS MEANT |
| | FOR MAIN HOUSE. PLEASE SEE THAT SD'S ARE |
| | NOW PLACED OUTSIDE FOR SLEEPING ROOMS |
| | ON DETACHED BLDG??? NOT TO BE INSTALLED. |
| | MISSING FOR INSIDE. |
| | |
| | 4)NOTE: PLEASE SHOW LOAD CALCUALTIONS |
| | FOR ENTIRE SERVICE PER 220. PLEASE SEE |
| | LOAD CALCS FOR AHU'S ETC ETC. |
| | |
| | 5)NOTE: PLEASE SEETHAT AN EXT CIRCUIT |
| | IS SHOWN FOR MAIN HOUSE AND ONLY ONE |
| | EXT SIGN SEEMS TO BE SHOWN? PLEASE SEE |
| | FIRE REVIEW COMMENT AND ALSO SEE 700.12E |
| | FOR CIRCUITING. |
| | |
| | 6)NOTE: PLEASE SEE THAT WATER HEATER(S) |
| | STILL SHOWN ON ELECTRICAL PANEL? ALSO |
| | SHOWN AS GAS? |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT. MAINS/PANELS/ BREAKER |
| | S ARE ALL TO BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT. 110.9/215.5 |
| | |
| | 8)NOTE: PLEASE CORREALET MECH/PLUMB/GAS |
| | PLAN WITH ELECTRICAL. SHOWS DRYER ALSO |
| | BEING GAS AND YET ON ELECTRICAL, THIS |
| | IS SHOWN AS ELEC?? |
| | |
| | 9)NOTE: PLEASE SEE THAT AHU'S ARE NOW |
| | SHOWN IN ATTIC SPACE, PLEASE SHOW LIGHT |
| | AND RECEPT REQ'D UNDER 210.63/210.70 |
| | |
| | 10)NOTE: PLEASE INDICATE INDIVIDUAL KW |
| | LOADS FOR AHU'S. |
| | |
| | 11)NOTE: PLEASE SEE FBC CHAPTER 34 |
| | 3401.7.2/3401.7.1 |
| | 104.1 CHANGE OF OCCUPANCY TEC. |
| | PLEASE SHOW EXISTING ELECTRIC AND KNOW |
| | THAT ALL EXISTING MUST BE BROUGHT UP TO |
| | CODE. |
| | |
| | 12)NOTE:PLEASE SEE COPY OF FS. 553.80(2) |
| | -(B) WITH RESPECT TO DESIGN PROFESSIONAL |
| | -S FOR PLAN REVIEWS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |