| 2003-07-30 00:00:00 | *********** UNSAT ******************* |
| | |
| | PLEASE SEE THAT PLANS ARE NOT COMPLETE |
| | FOR FULL REVIEW. |
| | |
| | 1)NOTE: PLEASE SHOW LOCATION FOR ALL |
| | SERVICE PANELS AND DISCONNECTS. |
| | PLEASE SHOW LOCATION OF MAIN SERVICE. |
| | |
| | 2)NOTE: PLEASE SEE RISER, SHOWS 400A |
| | MAIN FEEDING TWO SEPARATE PANELS, ONE |
| | 200A, ONE 150A? PLEASE SUBMIT PANEL |
| | SCHEDULE FOR 400A MAIN IF THIS A MDP? |
| | 215.5/110.9 |
| | PLEASE ALSO SUBMIT AIC RATING FOR 400A |
| | MAIN. |
| | |
| | 3)NOTE: PLEASE SEE MISSING PANELS AT |
| | 2-STORY APTS? PLEASE SEE 225.31 FOR |
| | MEANS OF DISCONNECT AT DETACHED STRUCT- |
| | -URES. |
| | |
| | 4)NOTE: PLEASE SUBMIT GROUNDING FOR |
| | ALL DEATCHED BLDGS PER 250-32. |
| | |
| | 5)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS PER 250.110 AND |
| | SIZE PER 250.122FOR ALL SUB-PANELS |
| | AFTER FIRST MEANS OF DISC. 250.24 |
| | |
| | 6)NOTE: PLEASE LIST ALL REQ`D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULE(S) |
| | PER 210.12 |
| | |
| | 7)NOTE: PLEASE ALSO SHOW ALL A/C UNITS |
| | AND DISC'S PER 440.11 |
| | RECEPTS NOW REQ'D FOR COND UNITS PER |
| | 210.63 UNDER NEW 2002 NEC. |
| | |
| | 8)NOTE: PLEASE CORRELATE RISER AND PANEL |
| | -BOARD "A", SHOWN AS 200A ON RISER AND |
| | AS 400A ON SCHEDULE? |
| | |
| | 9)NOTE: PLEASE SEE RISER, SHOWS ONE |
| | POOL PUMP, YET PANEL 'A' SHOWS 1-20A |
| | BRKR FOR ONE, PANEL 'B' SHOWS ANOTHER |
| | POOL PUMP W/ 2P-30A AND LOAD CALCS FOR |
| | PANEL 'B' SHOWS @ 1.5 KW?? PLEASE |
| | CORRELATE. |
| | |
| | 10)NOTE: PLEASE SEE MISSING SD`S. TO BE |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | NFPA-72 8-1.4.2 AND FBC |
| | |
| | 11)NOTE: PLEASE LIST THE REQ'D SMALL |
| | APPLIANCE CIRCUITS MISSING . 210.52/ |
| | 210.11C.1, 220.16 |
| | |
| | 12)NOTE: PLEASELIST THE REQ'D DEDICAT- |
| | -ED BATH CIRCUIT(S) 210.52D/ 210.11C.3 |
| | |
| | 13)NOTE: PLEASE SEE FBC CHAPTER 34, |
| | 3401.7.2, 3401.7.1 SEEFBC AND |
| | CITY-WIDE ADMIN CODE. 104.1 FOR |
| | CHANGE IN OCCUPANCY. |
| | PLEASE SHOW ALL EXISTING ELECTRICAL AS |
| | "E", PLEASE SHOW AS BRINGING UP TO CODE |
| | FOR ELECTRICAL. |
| | |
| | 14)NOTE: PLEASE CORRELATE ALLAHU LOADS |
| | , OCP, AWG. SHOWN AS 20A AND LOAD CALCS |
| | WAY EXCEED THESE. PLEASE SHOW LOADS FOR |
| | ALL AHU HEAT STRIPS. |
| | 240/424.3B |
| | |
| | 15)NOTE: PLEASE SEE MIN CIRCUIT FOR |
| | WASHER 20A/#12, SHOWN AS #14 |
| | |
| | 16)NOTE: PLEASE SEE GARAGE RECEPTS TO |
| | BE SHOWN AS GFI/GFI PROTECTED. 210.8 |
| | |
| | 17)NOTE: PLEASE CORRELATE PLANS, SHOWS |
| | GAS WATER HEATERS AND ELECTRICAL? |
| | |
| | PLEASE NOTE, DUE TO MANY CHANGES IN PLAN |
| | -S TO MEET NEC CODE COMPLIANCE, THERE |
| | MAY BE OTHER COMMENTS TO FOLLOW. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE ALSO GO OVER ENTIRE SET |
| | OF PLANS. |