Plan Review Notes
Plan Review Notes For Permit 03071415
Permit Number 03071415
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-11 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)TITLE BLOCK FOR THE ENGINEER IS
 REQUIRED TO BE ON THE PLAN; FAC61G15-
 23.002.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)PROVIDE THE RECEIPT FOR THE IMPACT
 FEES.
  
 4.)PROVIDE AREA CALCULATIONS ON THE
 PLAN - EXISTING, PROPOSED, NEW TOTAL.
 ADDITIONS OF GREATER THAN 25% ARE
 REQUIRED TO COMPLY WITH FBC3401.7.1.2.
  
 5.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 6.)WHEN RESUBMITTING, SIGN THE
 OWNER/AGENT LINE OF THE ENERGY CALC
 FBC13-101.2.
  
 7.)PROVIDE A ROOF FRAMING PLAN.
  
 8.)FIREBLOCKING SHALL BE PROVIDED IN
 ALL WALLS AND PARTITIONS, FBC705.3.
  
 9.)1 1/2" WATERSTOP REQUIRED, CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC,
 2111.1.9.
  
 10.)THIS PROPERTY IS IN AN AREA OF
 QUESTIONABLE SOILS.PROVIDE A SOILS
 INVESTIGATION FOR THE PROPOSED ADDITION.
 HAVE THE STRUCTURAL ENGINEER CERTIFY
 THAT THE SLAB AND FOOTER ARE EXISTING AS
 DRAWN ON THE PLAN.
  
 11.)ADDITIONAL FEES REQUIRED (VALUE
 ADJUSTMENT AND RADON).
  
 12.)CLARIFY - TWO PRODUCT APPROVALS
 WERE SUBMITTED FOR HORIZONTAL ROLLERS;
 IMPACT AND NON IMPACT.THERE ARE ONLY
 TWO WINDOWS ON THE PLAN.IS ONE OF EACH
 TO BE INSTALLED?
  
 13.)CLARIFY - TWO PRODUCT APPROVALS
 WERE SUBMITTED FOR THE SGDS.THE NON-
 IMPACT PRODUCT APPROVAL IS EXPIRED.
 WHAT ARE YOU INSTALLING?
  
 14.)IF YOU ARE INSTALLING IMPACT GLASS
 HURRICANE SHUTTERS ARE NOT REQUIRED.