| 2003-07-25 00:00:00 | FIRE RESCUE RECORDS INDICATE THAT THIS |
| | BUILDING WAS FORMERLY USED AS A |
| | ROOMING HOUSE. SINCE IT CAN BE |
| | CONSIDERED AN EXISTING ROOMING HOUSE |
| | NO FIRE SPRINKLER SYSTEM WILL BE |
| | REQUIRED. |
| | |
| | 1) PLANS MAKE NO REFERENCE ABOUT THE |
| | EXISTING FIRE ALARM SYSTEM. THE |
| | EXISTING SYSTEM MUST BE REPLACED IF |
| | IT IS STILL THE 110 VOLT USED |
| | PREVIOUSLY. SEPARATE PLANS AND PERMITS |
| | REQUIRED. A FIRE ALARM SYSTEM IS |
| | REQUIRED FOR ROOMING HOUSES. |
| | |
| | 2) THE EXISTING SMOKE DETECTORS IF |
| | ELECTRIC CONTAINED WITHIN THE |
| | SLEEPING ROOMS SHALL BE BROUGHT TO |
| | FULL WORKING ORDER. |
| | |
| | 3) NO MENTION ABOUT SELF-CLOSING |
| | DEVICES ON SLEEPING ROOM DOORS. |
| | |
| | 4) NO MENTION ABOUT PORTABLE FIRE |
| | EXTINGUISHERS. |
| | |
| | 5) NO EMERGENCY LIGHTS SHOWN. |
| | |
| | 6) DOORS ARE REQUIRED THAT PROVIDE AT |
| | LEAST A 30 MINUTE FIRE BARRIER ON THE |
| | INTERIOR STAIRS BOTH TOP AND BOTTOM. |
| | DOORS WERE PREVIOUSLY PRESENT AT THESE |
| | LOCATIONS. |
| | |
| | 7) ALL WALLS SHALL BE SMOKE RESISTANT. |
| | |
| | 8) NO INFORMATION CONCERNING INTERIOR |
| | FINISH FOR WALLS AND CEILINGS. |
| | |
| | 9) BATHROOM AND CLOSET DOORS SHALL |
| | ALLOW ENTRY FROM THE OUTSIDE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |