Plan Review Notes
Plan Review Notes For Permit 03071240
Permit Number 03071240
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-07-25 00:00:00FIRE RESCUE RECORDS INDICATE THAT THIS
 BUILDING WAS FORMERLY USED AS A
 ROOMING HOUSE. SINCE IT CAN BE
 CONSIDERED AN EXISTING ROOMING HOUSE
 NO FIRE SPRINKLER SYSTEM WILL BE
 REQUIRED.
  
 1) PLANS MAKE NO REFERENCE ABOUT THE
 EXISTING FIRE ALARM SYSTEM. THE
 EXISTING SYSTEM MUST BE REPLACED IF
 IT IS STILL THE 110 VOLT USED
 PREVIOUSLY. SEPARATE PLANS AND PERMITS
 REQUIRED. A FIRE ALARM SYSTEM IS
 REQUIRED FOR ROOMING HOUSES.
  
 2) THE EXISTING SMOKE DETECTORS IF
 ELECTRIC CONTAINED WITHIN THE
 SLEEPING ROOMS SHALL BE BROUGHT TO
 FULL WORKING ORDER.
  
 3) NO MENTION ABOUT SELF-CLOSING
 DEVICES ON SLEEPING ROOM DOORS.
  
 4) NO MENTION ABOUT PORTABLE FIRE
 EXTINGUISHERS.
  
 5) NO EMERGENCY LIGHTS SHOWN.
  
 6) DOORS ARE REQUIRED THAT PROVIDE AT
 LEAST A 30 MINUTE FIRE BARRIER ON THE
 INTERIOR STAIRS BOTH TOP AND BOTTOM.
 DOORS WERE PREVIOUSLY PRESENT AT THESE
 LOCATIONS.
  
 7) ALL WALLS SHALL BE SMOKE RESISTANT.
  
 8) NO INFORMATION CONCERNING INTERIOR
 FINISH FOR WALLS AND CEILINGS.
  
 9) BATHROOM AND CLOSET DOORS SHALL
 ALLOW ENTRY FROM THE OUTSIDE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910