| Plan Review Notes For Permit 03071240 |
| Permit Number |
03071240 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-23 00:00:00 | ************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SHOW CIRCUITING FOR ALL | | | EM/EXT LTS PER 700.12E | | | | | | 3)NOTE: PLEASE CLARIFY WHERE SWITCHING | | | CONTROLS ARE FOR STAIR LIGHTING ON | | | FIRST FLOOR. LIFE SAFETY 101 5-8 | | | | | | 4)NOTE: CIRCUITING FOR BATHS PER 210.11. | | | C.3, 210.52D | | | | | | 5)NOTE: PLEASE SEE MISSING SD`S INSIDE | | | AND OUTSIDE ALL SLEEPING RMS. NFPA-72 | | | 8-1.4.2 | | | | | | 6)NOTE: PLEASE SEE 210.52.C.1 FOR RECEPT | | | SPACING ON KITCEHN COUNTERSPACE. | | | GFI 210.8.A.6 | | | | | | 7)NOTE: PLEASE CLARIFY ILLUMINATION FROM | | | SECOND FLOOR OUTSIDE EXITING. LS101 5-8 | | | | | | 8)NOTE: PLEASE SUBMIT LOAD CALCS AND | | | SERVICE , NEW OR EXISTING? | | | | | | PLEASE NOTE, UNABLE TO DO A COMPLETE | | | REVIEW AT THIS TIME. PLEASE SUBMIT THE | | | ABOVE INFORMATION FOR REVIEW. IF THERE | | | ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|