Plan Review Notes
Plan Review Notes For Permit 03071240
Permit Number 03071240
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-05 00:00:00*******CORRECTIONS*******
  
 NOTE - THIS PLAN HAS BEEN REVIEWED AS
 AN R1 BOARDING HOUSE.THE OWNER HAS
 INDICATED THAT HE IS CHANGING THIS TO
 AN R3 SINGLE FAMILY DWELLING.SOME OF
 THE COMMENTS WILL NOT APPLY TO AN R3
 OCCUPANCY.DISREGARD ANY COMMENTS
 WHICH DO NOT APPLY IF THIS IS
 RESUBMITTED AS AN R3.
  
 1.)EACH SHEET OF PLANS PREPARED BY
 THE ENGINEER SHALL BE SEALED, SIGNED
 AND DATED.THE ENGINEER SHALL INCLUDE
 THEIR LICENSE NUMBER ON EACH SHEET.
 FAC61G15-23.002(1); SEE ATTACHED.
  
 2.)ACCORDING TO THE PALM BEACH COUNTY
 PROPERTY APPRAISER, THE BUILDING VALUE
 IS $23,901.THIS REPAIR HAS A VALUE
 WHICH EXCEEDS 50% OF THE EXISTING; MUST
 COMPLY WITH FBC 3401.7.2.6.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 4.)THIS JOB IS NOT COVERED BY FLORIDA
 STATUTE EXEMPTIONS FROM ARCHITECT
 LICENSURE.HAVE A LICENSED PROFESSIONAL
 PREPARE AND SEAL DRAWINGS; FS481.229.
  
 5.)BY FBC202 DEFINITION, A "ROOMING
 HOUSE" CONTAINS NOT MORE THAN FIVE
 GUEST ROOMS.THIS BUILDING WOULD BE
 CONSIDERED R1, BOARDING HOUSE, FBC311.2.
 INDICATE THE CORRECT OCCUPANCY
 CLASSIFICATION ON THE PLAN.
  
 6.)THE SCOPE OF WORK IS NOT CLEAR.
 HAVE THE PLAN INDICATE THE SCOPE OF
 WORK, TO BE CONSISTENT WITH THE PERMIT
 APPLICATION.FOR EXAMPLE, THE ELEVATION
 SHOWS A SHINGLE ROOF, BUT NO WORK TO BE
 DONE TO THE ROOF.APPLICATION SHOWS
 ROOF REPAIR.A FLOOR PLAN IS SHOWN; IS
 EVERYTHING EXISTING?
  
 7.)PROVIDE A HAND RAIL DETAIL; COMPLY
 WITH FBC 1007.5.
  
 8.)PROVIDE A DETAIL FOR THE CONCRETE
 STEPS, REAR EXIT DOOR, 1ST FLOOR.SHOW
 ALL DIMENSIONS, INCLUDING THE LANDING.
 STAIRS ARE REQUIRED TO HAVE HANDRAILS,
 FBC 1007.5.
  
 9.)PROVIDE A DETAIL FOR THE EXTERIOR
 STAIR, SHOWING ALL DIMENSIONS, INCLUDING
 THE LANDINGS.
  
 10.)PROVIDE A GUARD RAIL DETAIL FOR
 THE EXTERIOR STAIR LANDING; FBC1015,
 FBC1608.2.2.
  
 11.)FIREBLOCKING REQUIRED AT STAIRS
 FOR WOOD CONTRUCTION; FBC2305.1.4.
  
 12.)DRAFTSTOPPING REQUIRED; PROVIDE A
 SCHEDULE, FBC705.3.
  
 13.)FIRESTOP REQUIRED FOR WALLS; FBC
 705.3.
  
 14.)THE STAIR RAILING IS TO COMPLY
 WITH FBC1608.2.1.
  
 15.) PROVIDE A STRUCTURAL DETAIL FOR THE
 STAIRS.THERE IS A STAIR DETAIL BUT IT
 IS NOT CLEAR AS TO WHETHER THEY ARE
 EXISTING OR BEING REBUILT.
  
 14.) SLEEPING ROOMS ARE REQUIRED TO
 HAVE EMERGENCY EGRESS FBC1005.4; SHOW
 COMPLIANCE.
  
 15.)WINDOWS AT THE BATHTUBS ARE TO
 BE SAFETY GLASS, FBC2405.
  
 16.)THE NOTES STATE THAT THE EXISTING
 WINDOWS ARE IMPACT WITH PRODUCT
 APPROVALS.IS THIS CORRECT?HISTORIC
 MADE A NOTE THAT WINDOWS ARE TO BE
 REPAIRED, NOT REPLACED.CORRECT THE
 NOTES TO REFLECT THE SCOPE OF WORK.
  
 17.) SHOW ATTIC ACCESS SIZE, FBC2309.6.
  
 18.) SEPARATE PERMITS REQUIRED.
  
 19.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 20.) SOFFIT VENTS TO COMPLY WITH FBC
 2309.7.
  
 21.) CRAWL SPACE VENTILATION REQUIRED,
 FBC1804.6.3.1.
  
 22.) IMPACT PROTECTION REQUIRED FOR
 WINDOWS; FBC1606.1.4.PROVIDE TWO
 COPIES OF PRODUCT APPROVALS AND A
 HURRICANE SHUTTER ATTACHMENT SCHEDULE
 (IF EXISTING WINDOWS ARE NOT IMPACT).
  
 23.) 1 HOUR TENANT SEPARATION REQUIRED;
 FBC704.3.SHOW ON THE FLOOR PLAN AND
 PROVIDE A DETAIL.
  
 24.)A 36" MINIMUM CORRIDOR WIDTH IS
 REQUIRED, FBC TABLE 1004.SHOW
 COMPLIANCE ON THE PLAN.
  
 25.)EXIT ACCESS CORRIDOR IS REQUIRED
 TO HAVE 1 HR FIRE RATING, FBC TABLE
 704.2.4.
  
 26.) OPENINGS IN EXIT ACCESS DOORS ARE
 REQUIRED TO HAVE A 20 MINUTE OPENING
 PROTECTIVE, FBC TABLE 705.1.2.
  
 27.) TWO EXITS REQUIRED; FBC1004.2.
 SHOW COMPLIANCE.
  
 28.) SMOKE DETECTOR REQUIRED IN CLOSE
 PROXIMITY TO THE STAIR, FBC905.2.2.
  
 29.) SMOKE DETECTORS REQUIRED IN
 CORRIDORS, FBC905.2.2.
  
 30.) PROVIDE A DETAIL FOR THE STAIRS
 AND FRONT PORCH, INCLUDING STAIR RAILS,
 GUARD RAILS, STAIRS; FBC 1007.5, FBC
 1015, FBC1012.1.3.
  
 31.) STAIRWAYS ARE REQUIRED TO HAVE
 HANDRAILS ON EACH SIDE, FBC1007.5.2.
  
 32.) INTERIOR FINISHES REQUIRED TO
 BE CLASS B FOR EXITS AND EXIT ACCESS;
 CLASS C FOR OTHER SPACES, FBC TABLE
 803.3.PROVIDE PRODUCT INFORMATION.
  
 33.) PROVIDE PRODUCT INFORMATION FOR
 DOORS REQUIRED TO BE FIRE RATED.
  
 34.)IF THE INTERIOR STAIRS WILL BE
 USED AS A MEANS OF EGRESS, SHOW
 COMPLIANCE WITH FBC1006 AND FBC1007.
  
 35.)EXTERIOR STAIRS SHALL COMPLY WITH
 FBC1006 AND FBC1007.
  
 36.)ALL CHANGES TO THE PLAN REQUIRE
 APPROVAL BY THE HISTORIC PRESERVATION
 DIVISION.
  
 37.) IF ROOF SHINGLES ARE TO BE
 INSTALLED, PRODUCT APPROVALS ARE
 REQUIRED.THEY MAY BE SUBMITTED NOW
 FOR REVIEW OR WITH THE ROOF PERMIT
 APPLICATION.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER