Plan Review Notes
Plan Review Notes For Permit 03071169
Permit Number 03071169
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-11 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE STORM SHUTTERS
 INFORMATION WITH CLARIFICATION FOR
 INSTALLATION OF STORM SHUTTERS AT
 OPENING #6.
 A)IS THIS INSTALLATION FOR OPENING #7?
 SEE PLANS FOR CORRECT OPENING.
 B)CLARIFY INSTALLATION OF PANELS AT
 BASE OF WINDOW. PLANS SPECIFY 1X BUCK.
 HOW IS THE ANCHOR ATTACHED TO 1X BUCK?
 C)PROVIDE TWO COPIES WITH ORIGINAL
 SEAL. SIGNATURE AND DATE AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 2-PROVIDE TWO COPIES OF ENERGY CALCS
 WITH ORIGINAL SEAL, SIGNATURE & DATE
 AS REQUIRED BY CHAPTER 471 FL. STATUTE