| Plan Review Notes For Permit 03071140 |
| Permit Number |
03071140 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-18 00:00:00 | DENIED: | | | REFERENCE COMMENTS ON BUILDING PERMIT | | | 03040476. | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3. | | | | | | INDICATE SIZE AND MATERIAL OF THE O.A. | | | DUCT. | | | | | | INTAKE LOUVER SHALL BE SCREENED PER 2001 | | | FBC(M) TABLE 401.6.PLEASE INDICATE | | | SIZE OF INTAKE LOUVER. | | | | | | CONDENSER UNIT STAND SHALL COMPLY WITH | | | 2001 FBC TABLE 1511.7, SEE ATTACHED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|