| Plan Review Notes For Permit 03071078 |
| Permit Number |
03071078 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-11 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM REVIEW. | | | PLEASE SEE THAT SOME NOTES WERE NOT | | | ADRESSED. | | | | | | 2)NOTE: PLEASE SEE THAT SOME OCP DEVICES | | | SHOWN ON PANEL SCHEDULE HAVE NOW BEEN | | | CHANGED TO 2POLE BRKRS FOR SINGLE POLE | | | ITEMS? | | | | | | 3)NOTE: PLEASE "LIST THE REQ'D ARC FAULT | | | CIRCUITS ON PANEL SCHEDULES. 210.12 | | | NOT OUTLETS,, CIRCUITS. | | | 4)NOTE: PLEASE SEE THAT AIC RATING IS | | | NOW SHOWN FOR FOR METER? NEEDS TO BE | | | SHOWN FOR MAINS/ PANELS. 110.9/215.5 | | | | | | 5)NOTE: PLEASE SEE SERVICE AND NOTES | | | FROM FIRST REVIEW. SERVICE IS STILL | | | NOTED TO HAVE A 300A MAIN? BUTNONE | | | SHOWN ON RISER OR PLANS.?? | | | PLEASE SEE CONDCUTORS ETC . | | | PLEASE SEE ORIG COMMENTS. | | | 250.66/310.16/310.15/240ETC NEC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | PLEASE SEE ATTACHED LETTER WITH RESPECT | | | TO DESIGN PROFESSIONALS. REQ'D PER FS | | | 553.80(2)(B). | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|