| Date |
Text |
| 2003-08-08 00:00:00 | DENIED |
| | |
| | 1) SUBMIT COPY OF UNITY OF TITLE FOR THE |
| | TWO LOTS. |
| | |
| | 2) SUBMIT A SOIL BORING TEST REPORT AS |
| | REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| | |
| | 3) THE A/C AREA LISTED ON A-3 OF THE |
| | PLANS DOES NOT CORRESPOND WITH THE |
| | CONDITIONED AREA ON THE ENERGY CALCS. OR |
| | THE COUNTY IMPACT FEE STAMP. PLEASE |
| | CORRECT. |
| | |
| | 4) SPECIFY ON THE PLANS THAT THE WIRE |
| | MESH IN THE SLAB IS REQUIRED TO BE |
| | SUPPORTED ON APPROVED MATERIALS AT NO |
| | MORE THAN 3FT. OC. PER FBC 1909.3. |
| | |
| | 5) SPECIFY THE SIZE OF THE SOFFIT VENTS |
| | ON A-6. SEE FBC 2309.7.1. |
| | |
| | 6) CONFLICTING DIMENSIONS ARE SPECIFIED |
| | FOR THE STEEL COLUMN CAP IN DETAIL 1 ON |
| | G2. PLEASE CORRECT. |
| | |
| | 7) TWO DETAILS ARE LABELED 1 ON G2. |
| | |
| | 8) FBC1609.4 NO LONGER ALLOWS THE ONE- |
| | THIRD STRESS INCREASE FOR STEEL CALCS. |
| | FOR COMBINATION LOADS. PLEASE REVISE |
| | THE ANCHOR SCHEDULE ON G1 TO VALUES THAT |
| | DO NOT INCLUDE THE INCREASE. SEE 2003 |
| | USP CATALOG. |
| | |
| | 9) THE ENGINEER'S LICENSE NUMBER OR |
| | CERTIFICATE OF AUTHORIZATION IS REQUIRED |
| | TO BE IN THE TITLE BLOCK. SEE 61G15- |
| | 23.002 |
| | |
| | 10) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL MULLIONS |
| | - ARCHED TOP FIXED GLASS WINDOWS |
| | |
| | 11) SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. THE |
| | SHUTTER PLAN ON A-3 DOES NOT LIST THE |
| | FRENCH DOORS OR THE SIDELITES AT THE |
| | ENTRY DOOR. THE FOLLOWING INFORMATION IS |
| | REQUIRED: TYPE OF ANCHORS, SPACING OF |
| | ANCHORS, TYPE OF MOUNT, CONNECTION TYPE, |
| | SHUTTER SPAN, AND OPENING PRESSURES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |