| 2004-05-08 00:00:00 | ***********UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE SIZING OF AWG FOR |
| | AHU'S, SHOWS #10 W/ 60A OCP. PLEASE SEE |
| | 310.16, 424.3B ETC. |
| | THIS HAS BEEN NOTED AND COMMENTED ON |
| | THE PREVIOUS 4-REVIEWS. PLANS HAVE |
| | STILL NOT BEEN CORRECTED. ONE SET |
| | OF PLANS ARE BEING RETAINED FOR POSSIBLE |
| | REVIEW BY THE FBPE'S . |
| | PLEASE CORRELATE LOAD CALCULATIONS AND |
| | PANEL SCHEDULES FOR A/C EQUIPMENT. |
| | |
| | PLEASE SUPPLY ADDITIONL NEW SETS FOR |
| | REVIEW WHEN REVISION IS RESUBMITTED. |
| | |
| | 2)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | |
| | 3)NOTE: PLANS MUST BE SIGNED WITH A |
| | SIGNATURE FROM ENGINEER THAT CONTIANS |
| | A VISABLE FIRST AND LAST NAME. PLANS |
| | APPEARS TO HAVE INITIALS. IF THIS IS |
| | ACTUAL SIGNATURE, PLEASE SUBMIT A COPY |
| | OF LICENSE IN ORDER TO VERIFY LEGAL |
| | SIGNATURE. FS 471.025, FAC 61G15-23.002 |
| | PER FBPE'S. THIS VERIFICATION CAN BE |
| | KEPT IN FILE FOR FUTURE PROJECTS. |
| | PLANS ALSO MUST BE DATED WHEN SIGNED BY |
| | ENGINEER. FS 471.025 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |