| Date |
Text |
| 2003-10-20 00:00:00 | *****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)THE NOTICE OF COMMENCEMENT IS |
| | EXPIRED (OVER 90 DAYS, FS713.13). |
| | |
| | 3.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #3, NOT ADDRESSED.PROVIDE A COPY OF |
| | THE RECEIPT SHOWING THAT IMPACT FEES |
| | HAVE BEEN PAID. |
| | |
| | 4.)WALL SECTIONS STILL SAY "MATCH |
| | EXISTING", BUT A6 SHOWS THAT SOFFIT |
| | VENTS SHOULD BE 7X16 EVERY 12'.IS THIS |
| | THE EXISTING CONDITION?IF NOT, REVISE |
| | THE WALL SECTIONS.IF IT IS, MAKE A |
| | NOTE UNDER THE SOFFIT VENT CALCULATIONS. |
| | |
| | 5.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #6.AS DISCUSSED, THE MANUFACTURER |
| | DOES NOT ALLOW STRESS INCREASE FOR |
| | STEEL.IF THIS WAS THE ONLY ITEM ON THE |
| | LIST, THE PERMIT WAS TO BE ISSUED WITH |
| | A PROVISO THAT THE CONNECTOR TABLES BE |
| | REVISED.AS THERE ARE OTHER ELECTRICAL |
| | AND STRUCTURAL CORRECTIONS, PLEASE |
| | REVISE AT THIS TIME. |
| | |
| | 6.)SEE PREVIOUS LIST, ITEM #7, FIRE- |
| | BLOCK REQUIRED AT STAIRS,FBC2305.1.4(3). |
| | THE DETAIL SHOWN DOES NOT COMPLY WITH |
| | THE CODE. |
| | |
| | 7.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #8; 2-G1 WAS NOT CHANGED. |
| | |
| | 8.)SEE PREVIOUS LIST, ITEMS 10 AND 11, |
| | SHOW COMPLIANCE WITH FBC1608.2. |
| | |
| | 9.)SEE PREVIOUS LIST, ITEM 12, NOT |
| | ADDRESSED.MULLION PRODUCT APPROVALS |
| | ARE STILL STAPLED TO THE PLAN; STILL DO |
| | NOT SEE WHERE MULLIONS ARE USED ON THIS |
| | JOB.HOWEVER, THE OTHER PRODUCT |
| | APPROVALS REQUESTED ARE STILL NOT A PART |
| | OF THIS PACKAGE.WINDOWS AND IMPACT |
| | PROTECTION WILL REQUIRE A SEPARATE |
| | PERMIT IF PRODUCT APPROVALS ARE NOT |
| | SUBMITTED. |
| | |
| | 10.) ADDITIONAL FEES DUE. |
| | |
| | 11.) THERE IS A MECHANICAL PROVISO ON |
| | THE MECHANICAL PAGE.PLEASE ADDRESS |
| | AT THIS TIME, PER REQUEST OF THE |
| | MECHANICAL PLAN REVIEWER. |
| | |
| | WHEN RESUBMITTING, REPLACE SHEETS WHICH |
| | HAVE CHANGED WITH THE NEW SHEETS. SUBMIT |
| | THE OLD SHEETS SEPARATELY, CLEARLY |
| | MARKED.TO EXPEDITE PLAN REVIEW, |
| | INCLUDE A TRANSMITTAL SHEET EXPLAINING |
| | HOW EACH ITEM WAS ADDRESSED. |