| 2003-07-29 00:00:00 | ******CORRECTIONS******* |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC, FBC13-103.1.2. |
| | |
| | 3.)PROVIDE THE RECEIPT TO SHOW PAYMENT |
| | OF THE IMPACT FEES TO PALM BEACH CO. |
| | |
| | 4.)SOFFIT VENTS MUST COMPLY WITH |
| | FBC2309.7. |
| | |
| | 5.)DRAFTSTOPPING REQUIRED; SHOW A |
| | SCHEDULE AND DETAIL, FBC705.3. |
| | |
| | 6.)THE TRUSS ANCHOR SCHEDULE HAS |
| | VALUES FOR ATTACHMENTS WHICH EXCEED THE |
| | UPLIFT ALLOWED AS PER THE USP 2003 |
| | CATALOG.SEE PP 6-7, USP CATALOG, |
| | REGARDING STRESS INCREASES FOR STEEL. |
| | |
| | 7.)FIREBLOCK REQUIRED AT THE STAIRS, |
| | FBC2305.1.4(3). |
| | |
| | 8.)WINDOW BUCK DETAIL DOES NOT COMPLY |
| | WITH FBC1707.4.4.2, 2003 REVISION (G1). |
| | |
| | 9.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE STAIRS. |
| | |
| | 10.) PROVIDE A DETAIL FOR THE HANDRAIL. |
| | RAIL IS TO COMPLY WITH FBC1608.2.1. |
| | |
| | 11.) PROVIDE A DETAIL FOR THE GUARDRAIL; |
| | MUST COMPLY WITH FBC1608.2.2, FBC CH.10. |
| | |
| | 12.)MULLION PRODUCT APPROVALS WERE |
| | SUBMITTED.THERE WEREN'T ANY DOUBLE |
| | WINDOWS ON THE PLAN. |
| | |
| | 13.) SUBMIT ROOF PRODUCT APPROVALS, OR |
| | THEY MAY BE SUBMITTED WITH THE ROOF |
| | PERMIT APPLICATION. |
| | |
| | 14.)ADDITIONAL FEES (VALUE ADJUSTMENT, |
| | RADON); $133.70 |