| Date |
Text |
| 2005-10-08 00:00:00 | ********* UNSAT *********** |
| | |
| | PLEASE SEE THERE ARE ITEMS NOT CORRECT |
| | FROM REDLINED PLANS IN SEPT 04. |
| | |
| | 1)NOTE: PLEASE SEE MIN GROUNDING |
| | ELECTRODE CONDUCTOR TO BE SIZED PER |
| | 250.66 1/0 MIN. |
| | |
| | 2)NOTE: PLEASE SEE ARC FAULT PROTECTION |
| | IS STILL BEING SHOWN FOR RECEPTS ONLY. |
| | 210.12 2002 PLANS SUBMITTED FOR PERMIT |
| | AFTER JULY 1ST, 2003 WHEN CODE CHANGED |
| | TO 2002 NEC. |
| | |
| | 3)NOTE: PLEASE SEE MISSING SD'S REQUIRED |
| | IN EXISTING DWELLING INSIDE AND OUTSIDE |
| | ALL SLEEPING RMS. NFAP-72 8-1.4.2 |
| | CHAPTER 34 FBC. |
| | |
| | 4)NOTE: PLEASE SEE WHAT APPEARS TO BE A |
| | BATHRM IN NEW ADDTION IS REQUIRED TO |
| | INDICATE GFI RECEPT. 210.8 |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | 6)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | REQUIRED ALONG KTICHEN COUNTERSPACE. |
| | 210.52C1,210.8A6 |
| | |
| | 7)NOTE: PLEASE CORRELATE AND COMPLETE |
| | RISER DIAGRAM FOR CODE COMPLIANCE. |
| | PLEASE SHOW ALL CONDUCTORS. |
| | PLEASE SEE ONLY ONE 2/0 FOR 200A PANEL. |
| | PLEASE SEE CONDUCTOS FOR PANEL "C" ARE |
| | SHOWN AS 3/0'S FOR 100A OCP AND IN 1 1/4 |
| | PIPE. PLEASE SEE MIN SIZE REQUIRED FOR |
| | CONDUCTORS TO BE CALCULATED FROMNEC |
| | TABLES. |
| | PLEASE SEE FEEDERS INDICATE ON PANEL "B" |
| | TO FEED PANEL "C" DO NOT MEET CODE |
| | COMPLIANCE. 240.4,310.16 |
| | |
| | 8)NOTE: PLEASE SEE"HOT TUB" IS BEING |
| | SHOWN ON PANEL SCHEDULE, HOWEVER PLANS |
| | DO NOT SHOW THIS?? |
| | PLEASEALSO SEE PANEL SCHEDULE SHOWS |
| | 300A OCP?? ON #6?? |
| | 215.5,240.4,310.16 ETC. |
| | |
| | 9)NOTE: PLEASE SHOW ALL EXISTING |
| | DWELLING ELECTRICAL AS EITHER EXISTING |
| | MEETING 2002 NEC OR NEW TO BE BROUGHT UP |
| | TO CODE. |
| | FBC CHAPTER 34 ADDITIONS AND REMODELING |
| | EXISTING. |
| | THIS WAS REDLINED ON PLANS FROM SEPT 04. |
| | PLEASE SEE PLANS REFERENCE 2001?? |
| | 2002 NEC IS CODE IN EFFECT. |
| | |
| | 10)NOTE: PLEASE LIST THE REQUIRED |
| | DEDICATED CIRCUIT(S) FOR BATH(S). |
| | 210.52D,210.11C3, MUST BE 20A AND #12. |
| | |
| | 11)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS PER 250.110,250.122 |
| | 250.24 ETC. |
| | |
| | 12)NOTE: PLEASE INCLUDE NEW OR EXISTING |
| | SEC'S WHICH MEETS THE 350A SERVICE |
| | SHOWN. |
| | PLEASE INLCUDE SIZE OF RISER. |
| | 310.15B6,310.16, 240.4, 215.5 ETC. |
| | |
| | 13)NOTE: PLEASE SEE SWITCHES NOT SHOWN |
| | AS 3-WAYS, WHEN WIRING ON PLANS SHOULD |
| | INDICATE THIS. |
| | |
| | 14)NOTE: PLEASE SEE NUMEROUS BRKRS ON |
| | PANEL SCHEDULES WHICH DO NOT SEEM TO |
| | CORRELATE WITH AWG SHOWN. |
| | 30A OCP, #6, 15A, #12 |
| | |
| | 15)NOTE: PLEASE SEE MISSING FRONT GFI |
| | 210.52E |
| | |
| | 16)NOTE: PLEASE SEE MISSING EGRESS LT?? |
| | FRONT DOOR. 210.70 |
| | PLEASE SEE GFI REQUIRED IN GARAGE. |
| | 210.52G, 210.8 |
| | |
| | 17)NOTE: PLEASE SEE A GFI CIRCUIT IS |
| | BEING SHOWN AS "OPT" ON PANEL SCHEDULE?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |