Plan Review Notes
Plan Review Notes For Permit 03071035
Permit Number 03071035
Review Stop E
Sequence Number 5
Notes
Date Text
2005-10-08 00:00:00********* UNSAT ***********
  
 PLEASE SEE THERE ARE ITEMS NOT CORRECT
 FROM REDLINED PLANS IN SEPT 04.
  
 1)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR TO BE SIZED PER
 250.66 1/0 MIN.
  
 2)NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS STILL BEING SHOWN FOR RECEPTS ONLY.
 210.12 2002 PLANS SUBMITTED FOR PERMIT
 AFTER JULY 1ST, 2003 WHEN CODE CHANGED
 TO 2002 NEC.
  
 3)NOTE: PLEASE SEE MISSING SD'S REQUIRED
 IN EXISTING DWELLING INSIDE AND OUTSIDE
 ALL SLEEPING RMS. NFAP-72 8-1.4.2
 CHAPTER 34 FBC.
  
 4)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 BATHRM IN NEW ADDTION IS REQUIRED TO
 INDICATE GFI RECEPT. 210.8
  
 5)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 6)NOTE: PLEASE SEE MISSING GFI RECEPTS
 REQUIRED ALONG KTICHEN COUNTERSPACE.
 210.52C1,210.8A6
  
 7)NOTE: PLEASE CORRELATE AND COMPLETE
 RISER DIAGRAM FOR CODE COMPLIANCE.
 PLEASE SHOW ALL CONDUCTORS.
 PLEASE SEE ONLY ONE 2/0 FOR 200A PANEL.
 PLEASE SEE CONDUCTOS FOR PANEL "C" ARE
 SHOWN AS 3/0'S FOR 100A OCP AND IN 1 1/4
 PIPE. PLEASE SEE MIN SIZE REQUIRED FOR
 CONDUCTORS TO BE CALCULATED FROMNEC
 TABLES.
 PLEASE SEE FEEDERS INDICATE ON PANEL "B"
 TO FEED PANEL "C" DO NOT MEET CODE
 COMPLIANCE. 240.4,310.16
  
 8)NOTE: PLEASE SEE"HOT TUB" IS BEING
 SHOWN ON PANEL SCHEDULE, HOWEVER PLANS
 DO NOT SHOW THIS??
 PLEASEALSO SEE PANEL SCHEDULE SHOWS
 300A OCP?? ON #6??
 215.5,240.4,310.16 ETC.
  
 9)NOTE: PLEASE SHOW ALL EXISTING
 DWELLING ELECTRICAL AS EITHER EXISTING
 MEETING 2002 NEC OR NEW TO BE BROUGHT UP
 TO CODE.
 FBC CHAPTER 34 ADDITIONS AND REMODELING
 EXISTING.
 THIS WAS REDLINED ON PLANS FROM SEPT 04.
 PLEASE SEE PLANS REFERENCE 2001??
 2002 NEC IS CODE IN EFFECT.
  
 10)NOTE: PLEASE LIST THE REQUIRED
 DEDICATED CIRCUIT(S) FOR BATH(S).
 210.52D,210.11C3, MUST BE 20A AND #12.
  
 11)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS PER 250.110,250.122
 250.24 ETC.
  
 12)NOTE: PLEASE INCLUDE NEW OR EXISTING
 SEC'S WHICH MEETS THE 350A SERVICE
 SHOWN.
 PLEASE INLCUDE SIZE OF RISER.
 310.15B6,310.16, 240.4, 215.5 ETC.
  
 13)NOTE: PLEASE SEE SWITCHES NOT SHOWN
 AS 3-WAYS, WHEN WIRING ON PLANS SHOULD
 INDICATE THIS.
  
 14)NOTE: PLEASE SEE NUMEROUS BRKRS ON
 PANEL SCHEDULES WHICH DO NOT SEEM TO
 CORRELATE WITH AWG SHOWN.
 30A OCP, #6, 15A, #12
  
 15)NOTE: PLEASE SEE MISSING FRONT GFI
 210.52E
  
 16)NOTE: PLEASE SEE MISSING EGRESS LT??
 FRONT DOOR. 210.70
 PLEASE SEE GFI REQUIRED IN GARAGE.
 210.52G, 210.8
  
 17)NOTE: PLEASE SEE A GFI CIRCUIT IS
 BEING SHOWN AS "OPT" ON PANEL SCHEDULE??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  