| Plan Review Notes For Permit 03071035 |
| Permit Number |
03071035 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-11-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA STATUTES | | | | | | 1) FROM PREVIOUS REVIEW: SANITARY RISER | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN, | | | NOR DOES IT MEET CODE REQUIREMENTS. | | | THE BAR SINK IS NOT SHOWN ON THE SANT. | | | RISER DIAGRAM. THE WASH MACHINE AND BAR | | | SINK SHALL CONNECT DOWNSTREAM OF THE | | | BATHROOM FIXTURES. 909.1. THE SHOWER AND | | | BIDET ARE NOT VENTED. 901.2.1. THE BIDET | | | REQUIRES A TRAP, 1002.1 | | | SEE ORIGINAL PLAN FOR RED LINE CORRECT- | | | IONS GIVEN TO ASSIST IN SUBMITTING A | | | SANT. RISER THAT REFLECTS FLOOR PLAN AND | | | MEETS CODE REQUIREMENTS. | | | 2) SEE ATTACHED SHEET CONCERNING FLORIDA | | | STATUTE 533.80(2)(B) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|