| Plan Review Notes For Permit 03071035 |
| Permit Number |
03071035 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-11-07 00:00:00 | ************ UNSAT ************** | | | | | | PLEASE SEE THAT SOME NOTES FROM FIRST | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE 2002 NEC, ARC FAULT | | | PROTECTION IS NO LONGER JUST FOR RECEPTS | | | PLEASE SEE 210.12. PLEASE LIST ON PANEL | | | | | | SCHEDULE. | | | 2)NOTE: PLEASE SEE RECEPT NEXT TO BAR | | | SINK, GFI PER 210.8 | | | | | | 3)NOTE: PLEASE SHOW SERVICE ON PLANS, | | | PLANS SHOW ONE PANEL IN GARAGE ONLY? | | | PLEASE SEE RISER DIAGRAM. | | | 215.5 | | | | | | 4)NOTE: PLEASE SEE RISER SHOWS NEW | | | PANEL BUT NOTHING ON HOW THIS PANEL IS | | | BEING FED? CONDUCTORS, CONDUIT ETC ETC. | | | PLANS SHOWS 150 A SERVICE AND 200A MAINS | | | W/ 200A LOAD ETC? PLEASE CORRELATE | | | PLANS AND RISER TO NEC. 230.42, 240, | | | 310.15B6ETC. 215.5 | | | | | | 5)NOTE: PLEASE SEE AHU#2, SHOWS 10KW AND | | | 4.5 KW ETC. PLEASE CORRELATE. | | | | | | 6)NOTE: PLEASE SEE PLANS REF 2001 NEC, | | | WE ARE UNDER THE 2002 NEC. | | | | | | 7)NOTE: PLEASE SEEOTHER OCP/BRKR | | | SIZES ON PANEL SCHEDULE. | | | PLEASE CORRELATE OCP/KW/ AWG. | | | AHU'S PUMP' ETC. | | | | | | 8)NOTE: PLEASE SEE ATTACHED COPY OF | | | FS,553.80.(2)(B). | | | | | | PLEASE REMOVE OLD SHEETS AND INSERT NEW | | | SHEETS INTO COMPLETE STES FOR REVIEW AND | | | STAMPING. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|