2003-11-07 00:00:00************ UNSAT **************
  
 PLEASE SEE THAT SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE 2002 NEC, ARC FAULT
 PROTECTION IS NO LONGER JUST FOR RECEPTS
 PLEASE SEE 210.12. PLEASE LIST ON PANEL
  
 SCHEDULE.
 2)NOTE: PLEASE SEE RECEPT NEXT TO BAR
 SINK, GFI PER 210.8
  
 3)NOTE: PLEASE SHOW SERVICE ON PLANS,
 PLANS SHOW ONE PANEL IN GARAGE ONLY?
 PLEASE SEE RISER DIAGRAM.
 215.5
  
 4)NOTE: PLEASE SEE RISER SHOWS NEW
 PANEL BUT NOTHING ON HOW THIS PANEL IS
 BEING FED? CONDUCTORS, CONDUIT ETC ETC.
 PLANS SHOWS 150 A SERVICE AND 200A MAINS
 W/ 200A LOAD ETC? PLEASE CORRELATE
 PLANS AND RISER TO NEC. 230.42, 240,
 310.15B6ETC. 215.5
  
 5)NOTE: PLEASE SEE AHU#2, SHOWS 10KW AND
 4.5 KW ETC. PLEASE CORRELATE.
  
 6)NOTE: PLEASE SEE PLANS REF 2001 NEC,
 WE ARE UNDER THE 2002 NEC.
  
 7)NOTE: PLEASE SEEOTHER OCP/BRKR
 SIZES ON PANEL SCHEDULE.
 PLEASE CORRELATE OCP/KW/ AWG.
 AHU'S PUMP' ETC.
  
 8)NOTE: PLEASE SEE ATTACHED COPY OF
 FS,553.80.(2)(B).
  
 PLEASE REMOVE OLD SHEETS AND INSERT NEW
 SHEETS INTO COMPLETE STES FOR REVIEW AND
 STAMPING.
  