2003-07-24 00:00:00****************UNSAT **************
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF THE
 FAC 61G1-16.004 FOR REQ'D INFORMATION
 IN TITLE BLOCK.
  
 2)NOTE: PLEASE SEE 2001 FBC CHAPTER 34
 3401.7.1 PLEASE SHOW ALL EXSITINGS ROOMS
 BEING UPGRADED TO TODAYS NEC STANDARDS.
 RECEPTS, SWITCHES,LTS , WIRING ETC ETC.
  
 3)NOTE: PLEASE SUBMIT THE AIC RATING
 FOR NEW SERVICE EQUIPMENT.
  
 4)NOTE: PLEASE CLARIFY HOW MANY A/C
 SYSTEMS THERE ARE? SHOWS A AHU IN NEW
 ADDTION, BUT NOTHING SHOWN FOR DISC?
 440.11 AND LOAD CALCS?220
  
 5)NOTE: PLANS MENTION BEDROOM RECEPTS TO
 BE ARC FAULT TYPE. PLEASE LIST ALL THE
 REQ'D ARC FAULT PROTECTED CIRCUIT ON
 PANEL SCHEDULE INCLUDING ALL EXISTING
 BEDRROMS. 210.12
 AN ARC FAULT RECEPT IS NOT AVAILABLE
 AT THIS TIME.
  
 6)NOTE: PLEASE SHOW RECEPT NEXT TO BAR
 SINK AS GFI ALSO. 210.8
  
 7)NOTE: PLEASE SHOW SERVICE LOCATION
 /PANEL/ METER ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]