| Plan Review Notes For Permit 03071035 |
| Permit Number |
03071035 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-24 00:00:00 | ****************UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF THE | | | FAC 61G1-16.004 FOR REQ'D INFORMATION | | | IN TITLE BLOCK. | | | | | | 2)NOTE: PLEASE SEE 2001 FBC CHAPTER 34 | | | 3401.7.1 PLEASE SHOW ALL EXSITINGS ROOMS | | | BEING UPGRADED TO TODAYS NEC STANDARDS. | | | RECEPTS, SWITCHES,LTS , WIRING ETC ETC. | | | | | | 3)NOTE: PLEASE SUBMIT THE AIC RATING | | | FOR NEW SERVICE EQUIPMENT. | | | | | | 4)NOTE: PLEASE CLARIFY HOW MANY A/C | | | SYSTEMS THERE ARE? SHOWS A AHU IN NEW | | | ADDTION, BUT NOTHING SHOWN FOR DISC? | | | 440.11 AND LOAD CALCS?220 | | | | | | 5)NOTE: PLANS MENTION BEDROOM RECEPTS TO | | | BE ARC FAULT TYPE. PLEASE LIST ALL THE | | | REQ'D ARC FAULT PROTECTED CIRCUIT ON | | | PANEL SCHEDULE INCLUDING ALL EXISTING | | | BEDRROMS. 210.12 | | | AN ARC FAULT RECEPT IS NOT AVAILABLE | | | AT THIS TIME. | | | | | | 6)NOTE: PLEASE SHOW RECEPT NEXT TO BAR | | | SINK AS GFI ALSO. 210.8 | | | | | | 7)NOTE: PLEASE SHOW SERVICE LOCATION | | | /PANEL/ METER ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|