Plan Review Notes
Plan Review Notes For Permit 03071035
Permit Number 03071035
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-07 00:00:00******CORRECTIONS******
  
 1.)THERE ARE HOLDS ON THIS PROPERTY,
 SEE ATTACHED.
  
 2.)THE POOL IS TO BE PERMITTED
 SEPARATELY.REMOVE FROM THE PERMIT
 APPLICATION.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)THE SITE PLAN SHOWS "ONE STORY
 RESIDENCE"; SHOULD SHOW EXISTING AND
 PROPOSED.
  
 5.)IS THE PRIVACY WALL A PART OF THIS
 PERMIT?IF IT IS, IINDICATE AS PROPOSED
 AND INCLUDE ON THE FOUNDATION PLAN.THE
 FOOTER CANNOT ENCROACH THE PROPERTY
 LINE.INCLUDE A DETAIL FOR THE WALL.
 IS THE NEW CONCRETE DRIVE A PART OF THIS
 PERMIT?INCLUDE ON THE APPLICATION.
  
 6.) PROVIDE AREA CALCULATIONS ON THE
 PLAN; INCLUDE EXISTING AND PROPOSED.
 ADDITIONS OVER 25% MUST COMPLY WITH
 FBC3401.7.1.2.1 AS AMENDED 7/1/03.
  
 7.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED, AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 8.)ENERGY CALCS REQUIRED FBC13-103.1.2
 SIGN THE OWNER/AGENT LINE AS WELL AS
 THE PREPARER LINE OF THE ENERGY CALC.
  
 9.)ADDITIONAL FEES ARE REQUIRED DUE
 TO VALUE ADJUSTMENT.ADDITIONAL FEES
 MAY BE ADDED AFTER THE SCOPE OF WORK
 IS DETERMINED.ADJUSTMENT WAS MADE FOR
 THE ADDITION ONLY; NO INTERIOR
 RENOVATIONS, DRIVEWAY, OR ENTRY WALL
 AND GATES.PROVIDE AN ESTIMATED VALUE
 FOR THESE ITEMS, PROVIDING CONTRACTS IF
 AVAILABLE.
  
 10.) WILL THE EXISTING FOOTER AND TIE
 BEAM TIE INTO THE EXISTING?IF NOT,
 NOTE ON THE PLAN.
  
 11.) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING:
 ROOF TILE (MAY BE SUBMITTED WITH THE
 ROOF PERMIT APPLICATION)
 SINGLE HUNG WINDOW
 IMPACT PROTECTION FBC1606.1.4
 FRENCH DOORS
  
 12.) IF THE ROOF TILE IS FOAM SET (1-A1)
 PROVIDE PRODUCT APPROVALS FOR THE
 POLY FOAM.
  
 13.) CRAWL SPACE SHALL HAVE CROSS
 VENTILATION; SIZE TO CONFORM TO FBC
 1804.6.3.
  
 14.) WOOD FLOOR JOISTS TO BE OF
 NATURALLY DURABLE WOOD OR PRESSURE
 TREATED, FBC2304.3.4.
  
 15.) CHANGES DRAWN ON THE PLAN BY THE
 DESIGNER SHOULD BE INITIALED AND DATED.
  
 16.) SPECIFY A GIRDER CONNECTION ON
 THE ROOF FRAMING PLAN.
  
 17.) TRUSS ENGINEERING IS FOR 110 MPH
 WIND, SBCCI 97.THIS IS AN INCORRECT
 WIND AND CODE DESIGNATION, FBC FIGURE
 1606.
  
 18.) PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 19.) THIS PROPERTY IS IN A FLOOD ZONE.
 THE LOWEST FLOOR IS TO BE ELEVATED TO
 A MINIMUM OF 6" ABOVE THE BASE FLOOD
 ELEVATION; INDICATE ON THE PLAN, CITY
 OF WEST PALM BEACH MUNICIPAL CODE.
  
 20.) SUBMIT A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE, SEE ATTACHED.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]