2003-09-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTPER 1
  
 1) SECTION 1503.4.4 CONDENSATE SHALL
 DISCHARGE AT LEAST 1 FOOT FROM THE
 STRUCTURE SIDE WALL. SHOW DETAIL.
 2) SHT P1 W/HEATER EMERGENCY PAN DRAIN
 SHALL BE CPVC.
 3) FROM PREVIOUS REVIEW. SHOW P/T LINE
 PROVIDE AN ISOMETRIC AND INDICATE THE
 TERMINATION POINT FOR BOTH WATER HEATERS
 ALSO PROVIDE AN ISOMETRIC FOR THE PAN
 DRAIN WATER HEATER ON THE SECOND FLOOR.
 SHOW TERMINATION POINT FOR PAN DRAIN.
 SECTION 104.2.1
 4) FROM PREVIOUS REVIEW. THERMAL EXPAN-
 SION CONTROL REQUIRED, 607.3.2
  
 REVIEW BY KEN STEVENS