| Plan Review Notes For Permit 03070923 |
| Permit Number |
03070923 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTPER 1 | | | | | | 1) SECTION 1503.4.4 CONDENSATE SHALL | | | DISCHARGE AT LEAST 1 FOOT FROM THE | | | STRUCTURE SIDE WALL. SHOW DETAIL. | | | 2) SHT P1 W/HEATER EMERGENCY PAN DRAIN | | | SHALL BE CPVC. | | | 3) FROM PREVIOUS REVIEW. SHOW P/T LINE | | | PROVIDE AN ISOMETRIC AND INDICATE THE | | | TERMINATION POINT FOR BOTH WATER HEATERS | | | ALSO PROVIDE AN ISOMETRIC FOR THE PAN | | | DRAIN WATER HEATER ON THE SECOND FLOOR. | | | SHOW TERMINATION POINT FOR PAN DRAIN. | | | SECTION 104.2.1 | | | 4) FROM PREVIOUS REVIEW. THERMAL EXPAN- | | | SION CONTROL REQUIRED, 607.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|