| 2003-09-10 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE SERVICE ENT CONDUCTOR |
| | -S, SHOWS AN EQUIPMENT GROUNDING |
| | CONDUCTOR W/ SEC'S, PLEASE SEE 250.24 |
| | EGC IS ONLY INSTALLED AFTER FIRST MEANS |
| | OF DISC. |
| | |
| | 2)NOTE: PLEASE CLARIFY TWO WHAT APPEARS |
| | TO BE EM LT ON SECOND LEVEL OUTSIDE? |
| | PLEASE SEE THAT EGRESS LIGHTING IS NOW |
| | SHOWN FOR STAIRS OUTSIDE, HOWEVER |
| | SHOWS A SINGLE MEANS OF CONTROL FROM |
| | SECOND FLOOR AREA? LIFE SAFETY CODE |
| | WOULD REQUIRE EITHER AN AUTOMATED MEANS |
| | OF CONTROL(TIMECLOCK,PHOTOCELL) OR |
| | A MEANS OF CONTROL FROM FIRST FLOOR ANF |
| | AT EACH END OF STAIRS. |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RQATING FOR |
| | ALL NEW EQUIPMENT. MAINS, BRKRS AND |
| | PANELS ARE ALL TO BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT. 110.9/215.5 |
| | IT WAS NOTED ON THE BOTTOM OF PANEL |
| | THAT AIC RATING FOR PANELS ARE 10,000 |
| | PLEASE NOTE, ANY HANDWRITTEN CHANGES TO |
| | PLANS, MUST BE DONE IN INK AND ALSO |
| | MUST HAVE,,EACH CHANGE,, INITIALED, |
| | DATED BY ARCH/ENGINEER OF RECORD. |
| | PER FS'S 471, 481. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW.IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL.. |
| | |