2003-09-10 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SERVICE ENT CONDUCTOR
 -S, SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR W/ SEC'S, PLEASE SEE 250.24
 EGC IS ONLY INSTALLED AFTER FIRST MEANS
 OF DISC.
  
 2)NOTE: PLEASE CLARIFY TWO WHAT APPEARS
 TO BE EM LT ON SECOND LEVEL OUTSIDE?
 PLEASE SEE THAT EGRESS LIGHTING IS NOW
 SHOWN FOR STAIRS OUTSIDE, HOWEVER
 SHOWS A SINGLE MEANS OF CONTROL FROM
 SECOND FLOOR AREA? LIFE SAFETY CODE
 WOULD REQUIRE EITHER AN AUTOMATED MEANS
 OF CONTROL(TIMECLOCK,PHOTOCELL) OR
 A MEANS OF CONTROL FROM FIRST FLOOR ANF
 AT EACH END OF STAIRS.
  
 3)NOTE: PLEASE SUBMIT AIC RQATING FOR
 ALL NEW EQUIPMENT. MAINS, BRKRS AND
 PANELS ARE ALL TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110.9/215.5
 IT WAS NOTED ON THE BOTTOM OF PANEL
 THAT AIC RATING FOR PANELS ARE 10,000
 PLEASE NOTE, ANY HANDWRITTEN CHANGES TO
 PLANS, MUST BE DONE IN INK AND ALSO
 MUST HAVE,,EACH CHANGE,, INITIALED,
 DATED BY ARCH/ENGINEER OF RECORD.
 PER FS'S 471, 481.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL..
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]