Plan Review Notes
Plan Review Notes For Permit 03070923
Permit Number 03070923
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 1) SHT P1 DWV ISOMETRIC, CONDENSATE
 SHALL DRAIN SEPARATELY FROM THE BLDG. TO
 STORM, CATCH BASIN, OR DRYWELL NOT INTO
 SANITARY PER SECTION 90-125(B)(5).
 SUBMIT RISER AND DETAILS.
 2) SHT P1 DWV ISOMETRIC, WATER COOLER IS
 NOT VENTED. - NO HORIZONTAL DRY VENTS
 SECTION 905.3
 3) SHT P1 PLUMBING SPECIFICATIONS #4 AND
 WATER SUPPLY ISOMETRIC, AIR CHAMBERS ARE
 NOT APPROVED. DELETE FROM REFERENCE &
 ISOMETRIC. 604.9
 4) SHT P1 WATER HEATER, EMERGENCY PAN
 DRAIN IS REQUIRED. 504.8-INDICATE
 WHAT WILL HAPPEN TO THE RELIEF VALVE
 (T/P) DISCHARGE. SUBMIT DETAIL FOR PAN
 DRAIN LINE AND RELIEF VALVE DISCHARGE
 LINE. SHOW PIPE SIZE, MATERIAL, AND
 TERMINATION POINT FOR BOTH SYSTEMS.
 5) THERMAL EXPANSION CONTROL REQUIRED
 SECTION 607.3.2
 6) RPZ BACKFLOW REQUIRED. SECTION 608.13
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]