| Plan Review Notes For Permit 03070923 |
| Permit Number |
03070923 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | CITY WPB CODE | | | | | | 1) SHT P1 DWV ISOMETRIC, CONDENSATE | | | SHALL DRAIN SEPARATELY FROM THE BLDG. TO | | | STORM, CATCH BASIN, OR DRYWELL NOT INTO | | | SANITARY PER SECTION 90-125(B)(5). | | | SUBMIT RISER AND DETAILS. | | | 2) SHT P1 DWV ISOMETRIC, WATER COOLER IS | | | NOT VENTED. - NO HORIZONTAL DRY VENTS | | | SECTION 905.3 | | | 3) SHT P1 PLUMBING SPECIFICATIONS #4 AND | | | WATER SUPPLY ISOMETRIC, AIR CHAMBERS ARE | | | NOT APPROVED. DELETE FROM REFERENCE & | | | ISOMETRIC. 604.9 | | | 4) SHT P1 WATER HEATER, EMERGENCY PAN | | | DRAIN IS REQUIRED. 504.8-INDICATE | | | WHAT WILL HAPPEN TO THE RELIEF VALVE | | | (T/P) DISCHARGE. SUBMIT DETAIL FOR PAN | | | DRAIN LINE AND RELIEF VALVE DISCHARGE | | | LINE. SHOW PIPE SIZE, MATERIAL, AND | | | TERMINATION POINT FOR BOTH SYSTEMS. | | | 5) THERMAL EXPANSION CONTROL REQUIRED | | | SECTION 607.3.2 | | | 6) RPZ BACKFLOW REQUIRED. SECTION 608.13 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|