| Permit Number |
03070923 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-28 00:00:00 | DENIED: | | | | | | 1.PLAN SHEET M-1 INDICATES A RETURN | | | AIR TRANSFER FROM THE BATHROOM AREA. PER | | | 2001 FBC(M) TABLE 403.3, 50 CFM OF | | | EXHAUST PER WATER CLOSET OR URNIAL IS | | | REQUIRED FOR A BATHROOM.THIS SHALL NOT | | | BE RE-CIRCULATED. | | | | | | 2.RETURN/TRANSFER AIR DUCTS ARE NOT | | | SIZED. | | | | | | 3.NOTE 9 UNDER THE SPECFICATIONS | | | INDICATES THE CONDENSATE CAN TERMINATE | | | INTO THE SANITARY.PER CITY CODE SEC. | | | 90-125 (B) (5), CONDENSATE SHALL NOT | | | DISCHARGE INTO THE THE WASTE WATER | | | FACILTY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|