Plan Review Notes
Plan Review Notes For Permit 03070923
Permit Number 03070923
Review Stop M
Sequence Number 1
Notes
Date Text
2003-07-28 00:00:00DENIED:
  
 1.PLAN SHEET M-1 INDICATES A RETURN
 AIR TRANSFER FROM THE BATHROOM AREA. PER
 2001 FBC(M) TABLE 403.3, 50 CFM OF
 EXHAUST PER WATER CLOSET OR URNIAL IS
 REQUIRED FOR A BATHROOM.THIS SHALL NOT
 BE RE-CIRCULATED.
  
 2.RETURN/TRANSFER AIR DUCTS ARE NOT
 SIZED.
  
 3.NOTE 9 UNDER THE SPECFICATIONS
 INDICATES THE CONDENSATE CAN TERMINATE
 INTO THE SANITARY.PER CITY CODE SEC.
 90-125 (B) (5), CONDENSATE SHALL NOT
 DISCHARGE INTO THE THE WASTE WATER
 FACILTY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.