| Plan Review Notes For Permit 03070923 |
| Permit Number |
03070923 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-22 00:00:00 | ********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | TWO NEW MAIN DISCS. 110.9 | | | | | | 2)NOTE: PLEASE PROVIDE SIZE OF EXISTING | | | CONDUCTORS IN GUTTER/METE. | | | | | | 3)NOTE: PLEASE CLARIFY WHERE SIGN | | | CIRCUIT IS. PANEL SCHEDULE SHOWS REQ'D | | | CIRCUIT BUT NOT SHOWN ON PLANS. | | | | | | 4)NOTE: PLEASE SHOW "SHOW WINDOW" RECEPT | | | -S REQ'D PER 210.62 | | | | | | 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 230.42/215.3 | | | | | | 6)NOTE: PLEASE CLARIFY WATER HEATER ON | | | PANEL "A"/ SHOWN AS 1-POLE AND KW LOAD | | | IS SHOWN FOR A&B PHASE AS A 220V UNIT? | | | | | | 7)NOTE: PLEASE CLARIFY WHERE THE REQ'D | | | MEANS OF EGRESS LIGHTING IS FOR STAIRS? | | | TO SECOND FLOOR. LS 101 CHAP 5-8 | | | | | | 8)NOTE: PLEASE CLARIFY METHOD OF EQUIP-- | | | -MENT GROUNDING BETWEEN MAIN DSIC'S AND | | | PANELS A/B. 250.110/ 250.122 | | | | | | 9)NOTE: PLEASE SEE THAT LOAD CALCS ARE | | | TO BE SHOWN PER 220.3,220.10,220.11, | | | 220.13 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|